ESIE17-08
|
Part 2. Troubleshooting
2.4. Component checklist
Page 56
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
12. Power the Daikin unit.
13. Activate the inverter test (refer to
"Component checklist" on page 128
).
14. Check that all LED’s on the Inverter Analyzer are lit; if not, replace the inverter board (refer to
).
15. Switch off the Daikin unit with the field supplied circuit breaker.
16. Wait a few minutes and confirm that the LED's on the Inverter Analyzer are off.
17. Disconnect the Inverter Analyzer from the U V W wiring.
18. Reconnect the U V W leads to the compressor.
W
ARNING
Electrical shock hazard. Do not touch life wires.
C
AUTION
When wiring the compressor, observe UV W as indicated on the compressor.