Part 2. Troubleshooting
2.4. Component checklist
Page 52
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
2.4.2.4. Fan motor
PRELIMINARY ACTIONS
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
3. Remove plate work when required (refer to
).
PROCEDURE
1. Check the state of the propeller, replace the propeller if damaged, deformed, cracked or broken (refer to
fan blade assembly" on page 99
2. Check the motor shaft bearing friction, only perform electrical check if motor runs with low shaft bearing friction. Replace fan
motor if friction is abnormal (refer to
"Replacing DC fan motor assembly" on page 80
).
PRELIMINARY ACTIONS
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
3. Remove plate work when required (refer to
).
PROCEDURE
1. Check fuse on PCB, replace if blown, see table
"Component checklist" on page 128
2. Check if fan motor connector is plugged into PCB.
3. Power the Daikin unit.
4. Check power supply, the measured voltage must be 198 - 240 VAC, if not replace main PCB (refer to
).
Technical specification
Description
The motor has a single connector for DC power and the rotation
counter feed back from the integrated pulse generator
(4 pulses/revolution).
The fan motor runs on a fixed speed to supply the required air flow
rate.
Location
Piping diagram
Wiring diagram
Switch box
Component overview of unit
.
See
Check procedure
Mechanical check
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
When reconnecting a connector to the PCB, do not apply force, as this may damage the connector or connector pins of
the PCB.