ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 34 www.DaikinApplied.com
C
omprehensIve
d
aTa
T
ables
Table 17: Network Configuration Properties Inputs (NCIs) - Enfinity Single Stage Compressor, Continued
Point Name
l
on
W
orks
Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Configuration Property Inputs (NCIs)
Send Heartbeat
nciSndHrtBt
SCPTmaxSendTime
0 to 6553.4 sec
Default: 0
(Disabled)
No
Defines the maximum period of time that elapses before
the network variable outputs (NVOs) shown below are
automatically updated. Each NVO supported has a separate
timer associated with it. The BAS may be able to detect a
missing heartbeat from the unit controller to determine that
communication is lost and take corrective action. The value
of 0 disables the auto update feature.
Supported Variables
• nvoDischAirTemp
• nvoEffectOccup
• nvoEffectSetpt
• nvoFanSpeed
• nvoLocalSpaceTmp
• nvoSetpoint
• nvoSetptShift
• nvoSpaceTemp
• nvoUnitStatus
Device Software
Identification
(Major Version)
nciDevMajVer
SCPTdevMajVer
0 to 255
No
The software major version of the communication module
firmware.
Do not modify this configuration property.
Device Software
Identification
(Minor Version)
nciDevMinVer
SCPTdevMinVer
0 to 255
No
The software minor version of the communication module
firmware.
Do not modify this configuration property.
Software Jumpers
nciSoftJumpers
UCPTsoftJumpers
16 Characters
No
Sets the software jumper configuration. This property is not
implemented in unit controller software.
Unit Application
Identification
(Major Version)
nciUnitAppMajVer
UCPTunitAppMajVer
0 to 255
No
The major version of the unit controller software.
Do not modify this configuration property.
Unit Application
Identification
(Minor Version)
nciUnitAppMinVer
UCPTunitAppMinVer
0 to 255
No
The minor version of the unit controller software.
Unoccupied Setpoint
Differential
nciUnoccDiff
UCPTunOccDiff
2 to 10ºF
1.11 to 5.56ºC
Default:
2ºF / 1.11ºC
No
Sets the Unoccupied hysteresis that determines the Effective
OFF setpoints.
Interaction Rule
nciUnoccDiff < (unoccupied_cool – unoccupied_heat)
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable (NV) index number is a unique identifier for certain
L
on
W
orks
variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF file.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is offline).