ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
Table 17: Network Configuration Properties Inputs (NCIs) - Enfinity Single Stage Compressor, Continued
Point Name
l
on
W
orks
Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Configuration Property Inputs (NCIs)
Compressor Low
Suction Temp
Protection SP for
Glycol
nciLowTempProtGL
UCPTlowTempProtGL
0 to 50°F
-17.78 to 10°C
Default:
6.5ºF/-14.16ºC
No
nciLowTempProtGL is enabled by the unit controller JP3
jumper in the shorted position, which selects glycol as the
loop fluid.
Unit controller software v3 .1 and newer
• Temperature at which a Compressor Low Suction alarm
occurs in Heating mode when the loop fluid is glycol.
• nciLowTempProtGL does not apply to the
Dehumidification and Cooling modes, which use a fixed
28ºF low temp threshold regardless of the loop fluid
type.
Unit controller software v3 .0 and older
• Temperature at which a Compressor Low Suction alarm
occurs when the loop fluid is glycol.
Compressor Low
Suction Temp
Protection SP for
Water
nciLowTempProt
UCPTlowTempProt
0 to 50°F
-17.78 to 10°C
Default:
28ºF / -2.22ºC
No
nciLowTempProt is enabled by the unit controller JP3 jumper
in the open position, which selects water as the loop fluid.
Unit controller software v3 .1 and newer
• Temperature at which a compressor Low Suction alarm
occurs in the Heating mode when the loop fluid is water.
•
nciLowTempProt does not apply to the Dehumidification
and Cooling modes, which use a fixed 28ºF low temp
threshold regardless of the loop fluid type.
Unit controller software v3 .0 and older
• Temperature at which a Compressor Low Suction alarm
occurs when the loop fluid is water.
Compressor
Minimum OFF Timer
nciMinCompOffTmr
UCPTminCompOffTmr
0 to 1200 sec
Unit controller
v3.1 and newer
Default: 360 sec
Unit controller
v3.0 and older
Default: 180 sec
No
A countdown timer that defines the minimum period of time a
compressor must remain OFF before it is allowed to turn ON
again.
Compressor
Minimum ON Timer
nciMinCompOnTmr
UCPTminCompOnTmr
120 to 1200 sec
Default: 180 sec
No
A countdown timer that defines the minimum period of time a
compressor must remain ON before it is allowed to turn OFF
again.
Cooling Interstage
Timer
nciCoolIntStgTmr
UCPTcoolIntStgTmr
120 to 1200 sec
Default: 300 sec
No
A countdown timer that defines the minimum period of time
between turn-on of the cooling stages.
Cooling Setpoint
High Limit
nciClgSptHiLim
UCPTclgSptHiLim
50 to 95ºF
10 to 35ºC
Default:
90ºF / 32.22ºC
No
The maximum value of all the Occupancy Cooling setpoints.
The nciClgSptHiLim must be greater than nciClgSptLoLim.
Cooling Setpoint
Low Limit
nciClgSptLoLim
UCPTclgSptLoLim
50 to 95ºF
10 to 35ºC
Default:
55ºF / 12.78ºC
No
The minimum value of all Occupancy Cooling setpoints. It
also specifies the minimum allowed value of the nvoSetpoint
Long Range Setpoint Adjust. The nciClgSptLoLim must be
less than nciClgSptHiLim.
Heating Interstage
Timer
nciHeatIntStgTmr
UCPTheatIntStgTmr
120 to 1200 sec
Default: 300 sec
No
A countdown timer that defines the minimum period of time
between turn-on of the heating stages.
Heating Setpoint
High Limit
nciHtgSptHiLim
UCPThtgSptHiLim
50 to 95ºF
10 to 35ºC
Default:
95ºF / 35ºC
No
Maximum value of all Occupancy Heating setpoints. It also
specifies the maximum allowed value of the nvoSetpoint Long
Range Setpoint Adjust. The nciHtgSptHiLim must be greater
than nciHtgSptLoLim.
Heating Setpoint
Low Limit
nciHtgSptLoLim
UCPThtgSptLoLim
50 to 95ºF
10 to 35ºC
Default:
50ºF / 10ºC
No
Minimum value of all the Occupancy Heating setpoints. The
nciHtgSptLoLim must be less than nciHtgSptHiLim.
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable (NV) index number is a unique identifier for certain
L
on
W
orks
variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF file.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is offline).