ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 46 www.DaikinApplied.com
C
omprehensIve
d
aTa
T
ables
Table 20: Network Configuration Properties Inputs (NCIs) - SmartSource Single and Two Stage Compressor and Enfinity
Large Two Compressor, Continued
Point Name
l
on
W
orks
Variable
(NV Index)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Configuration Property Inputs (NCIs)
Device Software
Identification
(Minor Version)
nciDevMinVer
SCPTdevMinVer
0 to 255
No
The software minor version of the communication module
firmware.
Do not modify this configuration property.
Software Jumpers
nciSoftJumpers
UCPTsoftJumpers
16 Characters
No
Sets the software jumper configuration. This property is not
implemented in unit controller software.
Third Stage Heating
Setpoint Differential
nciStg3SptDiff
UCPTstg3SptDiff
1 to 10°F
0.55 to 5.56°C
Default:
6ºF / 3.33ºC
No
Used to determine the Third Stage Heating ON setpoints from
the Second Stage ON setpoints for units controlled by room
sensors.
Unit Application
Identification
(Major Version)
nciUnitAppMajVer
UCPTunitAppMajVer
0 to 255
No
The major version of the unit controller software.
Do not modify this configuration property.
Unit Application
Identification
(Minor Version)
nciUnitAppMinVer
UCPTunitAppMinVer
0 to 255
No
The minor version of the unit controller software.
Do not modify this configuration property.
Unoccupied Setpoint
Differential
nciUnoccDiff
UCPTunOccDiff
2 to 10ºF
1.11 to 5.56ºC
Default:
2ºF / 1.11ºC
No
Sets the Unoccupied hysteresis that determines the Effective
OFF setpoints.
Interaction Rule
nciUnoccDiff < (unoccupied_cool – unoccupied_heat)