www.DaikinApplied.com 53
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
Table 25:
Bit Description for SmartSource Single and Two Stage Compressor (Models GSH/GSV, GTH/GTV and GCV)
Bit
Number
Bit Description
Setting
Description
Unit Controller Jumpers
0
Compressor
ON (1)
Compressor request
1
Fan Main
ON (1)
Fan Main request
2
Reversing Valve
ON (1)
Heating position for compressor
OFF (0)
Cooling position for compressor
3
Pump Request / Isolation Valve
ON (1)
Water flow Is required
4
Alarm Output (A – Terminal)
ON (1)
Alarm output is energized with 24VAC when there is a fault
OFF (0)
Alarm output is de-energized when there is no fault
5
Remote Circuit #1 – Red LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
6
Remote Circuit #1 – Green LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
7
Remote Circuit #1 –Yellow LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
8
Room Sensor Status LED
ON (1)
Indicates the Room Sensor Status LED is ON steady. LED is ON when the unit
controller is in either the Occupied or Bypass modes
OFF (0)
Indicates the Room Sensor Status LED is either flashing or constantly OFF
I/O Expansion Module Outputs
9
Compressor – High Stage Capacity
ON (1)
Compressor – High Stage Capacity request
10
Auxiliary Heat Stage #1
ON (1)
Auxiliary Heat Stage #1 ON request
11
HGR/Waterside Economizer
ON (1)
HGR/Waterside Economizer request
12
Auxiliary Heat Stage #2
ON (1)
Auxiliary Heat Stage #2 ON request
13
Remote Circuit #2 – Red LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
14
Remote Circuit #2 – Green LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
15 (MSB)
1
Remote Circuit #2 –Yellow LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
1. MSB = Most Significant Bit
Table 26:
Bit Description for Enfinity Large Two Compressor (Models CCH/CCW and LVC/LVW)
Bit
Number
Bit Description
Setting
Description
Unit Controller Jumpers
0
Compressor #1
ON (1)
Compressor #1 request
1
Fan Main
ON (1)
Fan Main request
2
Reversing Valve #1
ON (1)
Heating position for compressor #1
OFF (0)
Cooling position for compressor #1
3
Pump Request/Isolation Valve
ON (1)
Water flow is required
4
Alarm Output (A – Terminal)
ON (1)
Alarm output is energized with 24VAC when there is a fault
OFF (0)
Alarm output is de-energized when there is no fault
5
Remote Circuit #1 – Red LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
6
Remote Circuit #1 – Green LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
7
Remote Circuit #1 –Yellow LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #1
8
Room Sensor Status LED
ON (1)
Indicates the room sensor Status LED is ON steady. LED is ON when the unit
controller is in either the Occupied or Bypass modes
OFF (0)
Indicates the room sensor Status LED is either flashing or constantly OFF
9
Compressor #2
ON (1)
Compressor #2 request
10
Reversing Valve #2
ON (1)
Heating position for compressor #2
OFF (0)
Cooling position for compressor #2
11
HGR/Waterside Economizer
ON (1)
HGR/Waterside Economizer request
12
Electric Heat/Hydronic Heat
ON (1)
Electric Heat/Hydronic Heat ON request
13
Remote Circuit #2 – Red LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
14
Remote Circuit #2 – Green LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
15 (MSB)
1
Remote Circuit #2 –Yellow LED
OFF (0) / ON (1)
Red, Green, and Yellow LEDs are used in combination to indicate the unit
controller Fault/Status mode for Circuit #2
1. MSB = Most Significant Bit
baC
neT
C
onfIguraTIon
and
C
ommIssIonIng