background image

2

Another important consideration in selecting a location for the
unit(s) is the angle to obstructions.  Either side adjacent the valves
can be placed toward the structure provided the side away from
the structure maintains minimum service clearance.  Corner in-
stallations are strongly discouraged.

12"

12"

60"

24"

This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. The foundation
slab should be a minimum of 6” wider than the unit in all direc-
tions. Ensure the foundation is sufficient to support the unit. A
concrete slab raised above ground level provides a suitable base.
The selected site should be no greater than 50’ below or 70’ above
the evaporator section. For optimum performance, the minimum
length interconnecting tubing is preferred. When possible mini-
mize the amount of bends and turns.

Rooftop Installations

If it is necessary to install this unit on a roof structure, ensure the
roof structure can support the weight and that proper consider-
ation is given to the weather-tight integrity of the roof. Since the
unit can vibrate during operation, sound vibration transmission
should be considered when installing the unit. Vibration absorb-
ing pads or springs can be installed between the condensing unit
legs or frame and the roof mounting assembly to reduce noise
vibration.

Rigging

To avoid possible injury or death, all panels must be in position 

and secured before lifting this equipment.

Use field-supplied spreader bars when lifting the unit to minimize
the possibility of lifting cable/straps damage. To protect the cabi-
net louvers, use protective material such as plywood behind the
cable/straps. Arrange the straps to form a central suspension
point. NOTE: When raising and setting the unit, observe all safety
rules. Remove shipping skid and all protection and lifting mate-
rial after the unit is in place.

Safe Refrigerant Handling

While these items will not cover every conceivable situation, they
should serve as a useful guide.

Summary of Contents for IOD-4003A

Page 1: ...ikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air c...

Page 2: ...n possible mini mize the amount of bends and turns Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper co...

Page 3: ...ps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8...

Page 4: ...ys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not...

Page 5: ...The distance from the building to the unit is 75 Calculate the minimum wire size assuming no more than 2 voltage drop MCA for 7 Ton 230V unit 43 3 from S R plate Applying previous table wire sizes les...

Page 6: ...tion and number of tubing fittings will have an impact on final unit charge amount Turn the electri cal power on and let the system run Wait for the refrigerant pressures to stabilize Charge Verificat...

Page 7: ...repairing leak 5 Dirty filters 5 Clean or replace filter 6 Coil frosted up 6 Defrost and clean coil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid l...

Page 8: ...HERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE Y YL YL L2 C T2 OUTDOOR POWER SUPPLY SEE RATING PLATE BK RD BK...

Reviews: