background image

3

To avoid possible explosion:

  Never apply flame or steam to a refrigerant cylinder. If you

     must heat a cylinder for faster charging, partially immerse

     it in warm water.

Never fill a cylinder more than 80% full of liquid refrigerant.

•   Never add anything other than R-410A to an R-410A cylinder.

     The service equipment used must be listed or certified for the
     type of refrigerant used.

•   Store cylinders in a cool, dry place. Never use a cylinder

     as a platform or a roller.

•  

•   

To avoid possible explosion, use only returnable (not disposable)

service cylinders when removing refrigerant from a system.

 •  Ensure the cylinder is free of damage which could lead to a

     leak or explosion.

•   Ensure the hydrostatic test date does not exceed 5 years.

•   Ensure the pressure rating meets or exceeds 400 lbs.

When in doubt, do not use cylinder.

Refrigerant Lines

NOTE: For improved refrigerant management, equip the evaporator
coil with a field-supplied thermal expansion valve (TXV) and the
liquid line with a field-supplied liquid line solenoid. Ensure the
solenoid is installed as close as possible to the evaporator coil to
prevent refrigeration migration in the compressor “OFF” cycle.

Use only refrigerant grade (dehydrated and sealed) copper tubing
to connect the condensing unit with the indoor evaporator.  After
cutting the tubing, install plugs to keep refrigerant tubing clean
and dry prior to and during installation.  Tubing should always be
cut square keeping ends round and free from burrs.  Clean the
tubing to prevent contamination.
Do NOT let refrigerant lines come in direct contact with plumbing,
ductwork, floor joists, wall studs, floors, and walls.  When run-
ning refrigerant lines through a foundation or wall, openings
should allow for sound and vibration absorbing material to be
placed or installed between tubing and foundation. Any gap be-
tween foundation or wall and refrigerant lines should be filled
with a pliable silicon-based caulk, RTV or a vibration damping
material. Avoid suspending refrigerant tubing from joists and studs
with rigid wire or straps that would come in contact with the
tubing. Use an insulated or suspension type hanger. Keep both
lines separate and always insulate the suction line.

Suct

Liq

Suct

Liq

Suct

Liq

7 1/2

1 1/8

 5/8

1 3/8

 5/8

1 3/8

 5/8

10

1 3/8

 5/8

1 5/8

 5/8

1 5/8

 5/8

Cond Unit

(Tons)

REFRIGERANT LINE LENGTH (ft)

0-24

25-49*

    50-74**

Line Diameter (In. OD)

Full rating line size

** Lines greater than 74 feet in length or vertical elevation changes more 
than 50 feet  refer to the Remote Cooling Service Manual or contact your 
distributor for assistance.

Insulation is necessary to prevent condensation from forming
and dropping from the suction line.  Armflex (or satisfactory
equivalent) with 3/8” min. wall thickness is recommended.  In
severe conditions (hot, high humidity areas) 1/2” insulation may
be required.  Insulation must be installed in a manner which
protects tubing from damage and contamination.
Where possible, drain as much residual compressor oil from ex-
isting systems, lines, and traps; pay close attention to low areas
where oil may collect.  NOTE: If changing refrigerant types, ensure
the indoor coil and metering device is compatible with the type of
refrigerant being used; otherwise, the indoor coil must be replaced.
To facilitate oil return to the compressor, a horizontal suction
line should be pitched (1/2” per 10’ toward the condensing unit.

Filter Drier and Sight Glass
A liquid line filter drier is factory installed. Field-install the sup-
plied sight glass/moisture indicator on the liquid line as close as
practical to the service valve.

Burying Refrigerant Lines

If burying refrigerant lines can not be avoided, use the following
checklist.

1. Insulate liquid and suction lines separately.

2. Enclose all underground portions of the refrigerant lines in

waterproof material (conduit or pipe) sealing the ends where
tubing enters/exits the enclosure.

3. If the lines must pass under or through a concrete slab,

ensure lines are adequately protected and sealed.

Refrigerant Line Connections

IMPORTANT: To avoid overheating the service valve, TXV valve,

or filter drier while brazing, wrap the component with a wet
rag, or use a thermal heat trap compound as recommended
by the compound manufacturer.  Use a brazing alloy of 2%
minimum silver content.  Do not use flux.

Summary of Contents for IOD-4003A

Page 1: ...ikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air c...

Page 2: ...n possible mini mize the amount of bends and turns Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper co...

Page 3: ...ps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8...

Page 4: ...ys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not...

Page 5: ...The distance from the building to the unit is 75 Calculate the minimum wire size assuming no more than 2 voltage drop MCA for 7 Ton 230V unit 43 3 from S R plate Applying previous table wire sizes les...

Page 6: ...tion and number of tubing fittings will have an impact on final unit charge amount Turn the electri cal power on and let the system run Wait for the refrigerant pressures to stabilize Charge Verificat...

Page 7: ...repairing leak 5 Dirty filters 5 Clean or replace filter 6 Coil frosted up 6 Defrost and clean coil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid l...

Page 8: ...HERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE Y YL YL L2 C T2 OUTDOOR POWER SUPPLY SEE RATING PLATE BK RD BK...

Reviews: