background image

7

TROUBLESHOOTING ANALYSIS TABLE

COMPLAINT

PROBABLE CAUSE

REMEDY

1. Excessive charge of refrigerant in system.

1. Purge or pump-down excessive charge.

2. Inadequate s upply of air acros s the

2. Make certain that coil is not fouled in any

condenser coil.

way, or that air is not re-circulating.

3. Non-condensate gases in the system.

3. Purge these gas es from the system.

Recharge system, if necessary.

1. System low on refrigerant.

1. Charge s ystem until sight glas s is clear of bubbles.

2. Compressor valves broken.

2. Replace c ompressor.

1. Liquid line v alve clos ed.

1. Open the liquid line valve.

2. Res tricted liquid  line.

2.  Replace filter-dryer.

3. The bulb of the thermal expansion valve

3. Detach the bulb from the suction line and hold

has  lost its charge.

in one hand. If no liquid refrigerant goes through

the valve, replace the valve.

4. System low on refrigerant.

4. Test the unit for leaks. Add refrigerant until sight

glass is free from bubbles, after repairing leak.

5. Dirty filters.

5. Clean or replace filter.

6. Coil frosted up.

6. Defrost and clean coil. Clean or replace filters.

7. Flash gas in the liquid line.

7. Excessive liquid line drop. Check liquid line size.

8. Quantity of air through evaporator not adequate.

8. Increas e the blower speed.

1. Expansion valve stuck open.

1. Correct valve action or replace the valve.

2. Expansion valve bulb not in contact with

2. Fasten bulb securely to suc tion line.

suction line.

3. Suction and/or discharge valve leaking or broken.

3. Replace c ompressor.

1. Disconnect switch open.

1. Close the disconnect switch.

2. Blow fuse or fuse at disconnect switch.

2. Check the caus e of failure and replace the fuse.

3. Thermostat set too high.

3. Adjust to lower temperature.

4. Selector switch in "Off" position.

4. Turn selector switch knob to "Cool" position.

5. Contactor  and/or relay c oils  burned  out.

5.  Replace c ontactor and/or  relay.

6. Loose or open electrical connection in either

6. Inspect and secure all electrical connections.

the control or power circuit.

5. Compres sor will not start.

1. High Head Pressure

2. Low Head Pressure

3. Low Suction Pressure

4. High Suction Pressure

Summary of Contents for IOD-4003A

Page 1: ...ikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air c...

Page 2: ...n possible mini mize the amount of bends and turns Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper co...

Page 3: ...ps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8...

Page 4: ...ys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not...

Page 5: ...The distance from the building to the unit is 75 Calculate the minimum wire size assuming no more than 2 voltage drop MCA for 7 Ton 230V unit 43 3 from S R plate Applying previous table wire sizes les...

Page 6: ...tion and number of tubing fittings will have an impact on final unit charge amount Turn the electri cal power on and let the system run Wait for the refrigerant pressures to stabilize Charge Verificat...

Page 7: ...repairing leak 5 Dirty filters 5 Clean or replace filter 6 Coil frosted up 6 Defrost and clean coil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid l...

Page 8: ...HERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE Y YL YL L2 C T2 OUTDOOR POWER SUPPLY SEE RATING PLATE BK RD BK...

Reviews: