background image

5

To avoid the risk of fire or equipment damage, use copper

conductors.

NOTICE

Units with reciprocating compressors and non-bleed TXV’s require

a Hard Start Kit.

This unit is designed for three phase operation. DO NOT OPERATE
ON A SINGLE PHASE POWER SUPPLY. Measure the power supply to
the unit. The supply voltage must be in agreement with the unit
rating plate power requirements.

RATED 

VOLTAGE

MINIMUM SUPPLY

VOLTAGE

MAXIMUM SUPPLY

VOLTAGE

208/230V

197

253

460V

414

506

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.  Con-
sult the NEC, CEC, and all local codes to determine the correct wire
gauge and length. The wire size must be sufficient to carry the
Minimum Circuit Ampacity (MCA) listed on the serial plate.
The supply voltage can be unbalanced (phase to phase) within
2%.  The following formula can be used to determine the percent-
age of voltage unbalance for your unit.

Percentage
Voltage
Unbalance

=

Max. Voltage Deviation From

Average Voltage
Average Voltage

Example:

L1

L2

 

=

 

220V

L2

L3

 

=

 

216V

Average

 

Voltage = (220

 

+

 

216

 

+

 

213)/3

=

649/3

Maximum

 

Deviation

 

from

 

Average

= 220

 ‐ 

216

 

=

 

4

%

 

Voltage

 

Unbalance

= 100

 

x

 

(4/216)

= 400/216

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

*Based on NEC 1996

MAXIMUM ALLOWABLE LENGTH IN FEET

TO LIMIT VOLTAGE DROP TO 2%

Minimum Circuit Ampacity (MCA)

Wire Size

(AWG)

Example:

A

 

7

 

½

 

Ton

 

unit

 

is

 

to

 

be

 

installed.

 

The

 

distance

 

from

 

the

 

building

 

to

 

the

 

unit

 

is

 

75’.

 

Calculate

 

the

 

minimum

 

wire

 

size

 

assuming

 

no

 

more

 

than

 

2%

 

voltage

 

drop.

MCA

 

for

 

7

   

Ton

 

230V

 

unit

 

=

 

43.3

 

(from

 

S&R

 

plate).

Applying

 

previous

 

table

 

wire

 

sizes

 

less

 

than

 

#8

 

AWG

 

cannot

 

be

 

used

 

for

 

circuits

 

which

 

have

 

a

 

rating

 

of

 

45A.

 

The

 

#8

 

wire

 

is

 

not

 

suitable

 

since

 

the

 

maximum

 

length

 

for

 

a

 

45A

 

circuit

 

is

 

68’.

 

Solution:

 

Use

 

a

 

#6

 

AWG

 

wire

 

suitable

 

up

 

to

 

110’.

 

NOTE:

 

It

 

is

 

the

 

contractors’s

 

responsibility

 

to

 

follow

 

the

 

NEC

 

(USA)

 

or

 

CEC

 

(Canada)

 

when

 

sizing

 

the

 

service

 

wire

 

for

 

this

 

unit.

½

Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit.  Refer to the installation
instructions supplied with the indoor furnace/air handler for spe-
cific wiring connections and indoor unit configuration.  Likewise,
consult the instructions packaged with the thermostat for mount-
ing and location information.

Overcurrent Protection

The following overcurrent protection devices are approved for
use.

Time delay fuses

HACR type circuit breakers

These devices have sufficient time delay to permit the motor-com-
pressor to start and accelerate its load.
Refer to the unit serial plate and this table for the maximum
overcurrent protection permitted.
Run all line voltage wiring a conduit from the service disconnect
box to the unit. Refer to the NEC (USA) or CEC (Canada) codes for
the correct size conduit based on the wire size. The conduit enters
the control box through the hole provided in the bottom. NOTE:
The control box hole is sized for 3/4” conduit. If permitted by
code, a flexible conduit is preferred to minimize vibration trans-
mission from the unit to the building.
Connect the line voltage wires to the L1, L2, and L3 terminals of the
definite purpose contactor (located in the unit control box). Refer
to the wiring diagram attached to the unit when making these
connections.

Summary of Contents for IOD-4003A

Page 1: ...ikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air c...

Page 2: ...n possible mini mize the amount of bends and turns Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper co...

Page 3: ...ps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8...

Page 4: ...ys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not...

Page 5: ...The distance from the building to the unit is 75 Calculate the minimum wire size assuming no more than 2 voltage drop MCA for 7 Ton 230V unit 43 3 from S R plate Applying previous table wire sizes les...

Page 6: ...tion and number of tubing fittings will have an impact on final unit charge amount Turn the electri cal power on and let the system run Wait for the refrigerant pressures to stabilize Charge Verificat...

Page 7: ...repairing leak 5 Dirty filters 5 Clean or replace filter 6 Coil frosted up 6 Defrost and clean coil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid l...

Page 8: ...HERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE Y YL YL L2 C T2 OUTDOOR POWER SUPPLY SEE RATING PLATE BK RD BK...

Reviews: