background image

4

1. The ends of the refrigerant lines must be cut square, de-

burred, cleaned, and be round and free from nicks or dents.
Any other condition increases the chance of a refrigerant
leak.

2. This unit is factory shipped with a holding charge. “Sweep”

the refrigerant line with nitrogen or inert gas during brazing
to prevent the formation of copper-oxide inside the refriger-
ant lines.

3. After brazing, quench the joints with water or a wet cloth to

prevent overheating of the service valve.

4. Ensure the filter drier paint finish is intact after brazing.  If

the paint of the steel filter drier has been burned or chipped,
repaint or treat with a rust preventative.  This is especially
important on suction line filter driers which are continually
wet when the unit is operating.

NOTE:  Be careful not to kink or dent refrigerant lines.  Kinked or
dented lines will cause poor performance or compressor damage.

Do NOT make final refrigerant line connection until plugs are
removed from refrigerant tubing.

NOTE:  Before brazing, verify indoor piston size by checking the
piston kit chart packaged with indoor unit.

Leak Testing (Nitrogen or Nitrogen-Traced)

To avoid the risk of fire or explosion, never use oxygen, high
pressure air or flammable gases for leak testing of a refrigeration
system.

Pressure test the system using dry nitrogen and soapy water to
locate leaks.  If you wish to use a leak detector, charge the system
to 10 psi using the appropriate refrigerant then use nitrogen to
finish charging the system to working pressure then apply the
detector to suspect areas. If leaks are found, repair them. After
repair, repeat the pressure test. If no leaks exist, proceed to sys-
tem evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed to contain
the charge within the unit.  The unit is shipped with the valve
stems closed and caps installed.  Do not open valves until the
system is evacuated.

1. Connect the vacuum pump with 250 micron capability to the

service valves.

2. Evacuate the system to 250 microns or less using suction

and liquid service valves.  Using both valves is necessary as
some compressors create a mechanical seal separating the
sides of the system.

3. Close pump valve and hold vacuum for 10 minutes.  Typi-

cally pressure will rise during this period.

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

AC

U

U

M

 

IN

 

M

IC

RON

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to startup.

• If pressure rises above 1000 microns but holds steady be-

low 2000 microns, moisture and/or noncondensibles may
be present or the system may have a small leak.  Return to
step 2: If the same result is encountered check for leaks as
previously indicated and repair as necessary then repeat
evacuation.

If pressure rises above 2000 microns, a leak is present.  Check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

Refer to the Remote Condensing Unit Service Manual for more
detailed instructions on system evacuation, preliminary charge
adjustment, and final charge adjustment.

Electrical Connections

HIGH VOLTAGE! 

Disconnect ALL power before servicing.
Multiple power sources may be present. Failure to do

so may cause property damage, personal injury or

death due to electric shock. Wiring must conform with

NEC or CEC and all local codes. Undersized wires could cause

poor equipment performance, equipment damage or fire.

Summary of Contents for IOD-4003A

Page 1: ...ikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air c...

Page 2: ...n possible mini mize the amount of bends and turns Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper co...

Page 3: ...ps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8...

Page 4: ...ys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not...

Page 5: ...The distance from the building to the unit is 75 Calculate the minimum wire size assuming no more than 2 voltage drop MCA for 7 Ton 230V unit 43 3 from S R plate Applying previous table wire sizes les...

Page 6: ...tion and number of tubing fittings will have an impact on final unit charge amount Turn the electri cal power on and let the system run Wait for the refrigerant pressures to stabilize Charge Verificat...

Page 7: ...repairing leak 5 Dirty filters 5 Clean or replace filter 6 Coil frosted up 6 Defrost and clean coil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid l...

Page 8: ...HERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE Y YL YL L2 C T2 OUTDOOR POWER SUPPLY SEE RATING PLATE BK RD BK...

Reviews: