background image

English

1

VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1

2. BEFORE INSTALLATION ................................................ 2

3. SELECTING INSTALLATION SITE ................................. 3

4. PREPARATIONS BEFORE INSTALLATION.................... 4

5. INDOOR UNIT INSTALLATION ....................................... 5

6. REFRIGERANT PIPING WORK ..................................... 5

7. DRAIN PIPING WORK .................................................... 6

8. ELECTRIC WIRING WORK ............................................ 8

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER........................................ 8

10. FIELD SETTINGS ......................................................... 11

11. TEST OPERATION ....................................................... 11

1.

SAFETY PRECAUTIONS

Please read these “SAFETY PRECAUTIONS” carefully before 
installing air conditioning equipment and be sure to install it cor-
rectly.
After completing installation, conduct a trial operation to check 
for faults and explain to the customer how to operate the air con-
ditioner and take care of it with the aid of the operation manual. 
Ask the customer to store the installation manual along with the 
operation manual for future reference.

This air conditioner comes under the term “appliances not 
accessible to the general public”.

This unit is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

Meaning of WARNING and CAUTION notices

WARNING

 ............. Failure to follow these instructions 

properly may result in personal injury 
or loss of life.

CAUTION

 .............. Failure to observe these instructions 

properly may result in property dam-
age or personal injury, which may be 
serious depending on the circum-
stances.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work.
Do not attempt to install the air conditioner yourself. Improper 
installation may result in water leakage, electric shocks or 
fire.

• Install the air conditioner in accordance with the instructions 

in this installation manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage. When the air conditioner is to be 
installed in a small room, it is necessary to take proper mea-
sures so that the amount of any leaked refrigerant does not 
exceed the concentration limit in the event of a leakage. 
Otherwise, this may lead to an accident due to oxygen deple-
tion. 

• Be sure to use only the specified accessories and parts for 

installation work. 
Failure to use the specified parts may result in the unit falling, 
water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit. 
A foundation of insufficient strength may result in the equip-
ment falling and causing injury.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit 
falling and causing accidents.

• Make sure that a separate power supply circuit is provided for 

this unit and that all electrical work is carried out by qualified 
personnel according to local laws and regulations and this 
installation manual. 
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are 

used, and that there is no strain on the terminal connections 
or wires.
Improper connections or securing of wires may result in 
abnormal heat build-up or fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in 
electric shocks, fire or the terminals overheating. 

• If refrigerant gas leaks during installation, ventilate the area 

immediately.  
Toxic gas may be produced if the refrigerant comes into con-
tact with fire.

• After completing installation, check for refrigerant gas leak-

age.
Toxic gas may be produced if the refrigerant gas leaks into 
the room and comes into contact with a source of fire, such 
as a fan heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical 

parts.

• Do not touch the switch with wet fingers.

Touching the switch with wet fingers can cause electric shock.

• Be sure to earth the air conditioner. 

Do not earth the unit to a utility pipe, lightning conductor or 
telephone earth lead.
Imperfect earthing may result in electric shocks or fire. 
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping to ensure proper drainage and insulate 
piping to prevent condensation. 
Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor and outdoor units, power cord and connect-

ing wires at least 1 meter away from televisions or radios to 
prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 
1 meter may not be sufficient to eliminate noise.)

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as 
possible.

01_EN_3P233622-5F.fm  Page 1  Thursday, December 18, 2008  4:21 PM

Summary of Contents for FXSN100AV1

Page 1: ...ONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KU...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents...

Page 4: ...st be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit inside its packaging while moving until reach ing the install...

Page 5: ...ual Installation manual Sealing material Small 35 150 Quantity 6 pcs Shape Model Min height above ceiling Air inlet panel Canvas connection for air inlet panel Color White FXSN20 25 32AV1 350mm or mor...

Page 6: ...shortened Indoor units should be installed as far away from fluorescent light ing as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight...

Page 7: ...the screws as shown in the drawing The paper pattern for installation is marked for 3 types of ceil ing openings Read the notations on the paper pattern care fully when installing 6 REFRIGERANT PIPIN...

Page 8: ...to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGER ANT PI...

Page 9: ...rainage flow during COOL running explained under TEST OPERATION WHEN ELECTRIC WIRING WORK IS NOT FINISHED Remove the electric parts box lid connect a power supply and remote controller to the terminal...

Page 10: ...wn below Be sure to adhere it to avoid water from outside unit CAUTION When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make ap...

Page 11: ...e of the sort could damage the entire system 7 Use only specified wire and tightly connect wires to termi nals Be careful wires do not place external stress on termi nals Keep wiring in neat order and...

Page 12: ...llowing table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation...

Page 13: ...11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid cryst...

Page 14: ...0901 FS HT 3P233622 5F EM08A072B...

Reviews: