background image

English

3

• Screws for fixing panels are attached to  decoration panel.

2-4

OPTIONAL ACCESSORIES

• Parts listed on the below table are required with this indoor 

unit.

Table 1

A minimum height of 425mm from the ceiling is required to 
install the canvas connection for the air inlet panel.

• These are two types of remote controllers: wired and wire-

less. Select a remote controller from Table 2 according to 
customer request and install in an appropriate place.

Table 2

NOTE

• If the you wishes to use a remote controller that is not listed 

above, select a suitable remote controller after consulting 
catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL 
CARE DURING CONSTRUCTION AND CHECK 
AFTER INSTALLATION IS FINISHED.

a. Items to be checked after completion of work

b. Items to be checked at time of delivery

Also review the “SAFETY PRECAUTIONS”

c. Points for explanation about operations

2-5

NOTES TO INSTALLER 

Be sure to instruct customers how to properly operate the 
unit (especially cleaning filters, operating different functions, 
and adjusting the temperature) by having them carry out 
operations themselves while looking at the manual.

3.

SELECTING INSTALLATION SITE 

Please attach additional thermal insulation material to the unit 
body when it is believed that the relative humidity in the ceiling 
exceeds 80%. Use glass wool, polyethylene foam, or similar with 
a thickness of 10 mm or more as thermal insulation material.

(1) Select an installation site where the following condi-

tions are fulfilled and that meets with your customer’s 
approval. 

• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.

Name

Screws for fixing the 

paper pattern for 

installation

(Other)

• Operation manual

• Installation manual

• Sealing material 

(Small 35×150)

Quantity

6 pcs.

Shape

Model

Min. height above 

ceiling

Air inlet panel

Canvas connection 

for air inlet panel

Color

White

FXSN20 · 25 · 32AV1

350mm or more

BYBS32D

Installation not 

required

425mm or more  

KSA25K36

FXSN40 · 50AV1

350mm or more

BYBS45D

Installation not 

required

425mm or more  

KSA25K56

FXSN63 · 100AV1

350mm or more

BYBS125D

Installation not 

required

425mm or more  

KSA25K160

Remote controller

Wired type

Wireless type

Items to be checked

If not properly done, what is 
likely to occur

Check

Are the indoor, outdoor and 
BEV unit fixed firmly?

The units may drop, vibrate 
or make noise.

Is the gas leak test finished? 

It may result in insufficient 
cooling.

Is the unit fully insulated?

Condensate water may drip.

Dose drainage flow 
smoothly?

Condensate water may drip.

Dose the power supply volt-
age correspond to that 
shown on the name plate?

The unit may malfunction or 
the components burn out.

Are wiring and piping cor-
rect?

The unit may malfunction or 
the components burn out.

Is the unit safely grounded?

Dangerous at electric leak-
age.

Is wiring size according to 
specifications?

The unit may malfunction or 
the components burn out.

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
instruction manual to your customer?

Did you hand the instruction manual over to your cus-
tomer?

The items with 

WARNING and 

CAUTION marks in 

the instruction manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
instruction manual.

01_EN_3P233622-5F.fm  Page 3  Thursday, December 18, 2008  4:21 PM

Summary of Contents for FXSN100AV1

Page 1: ...ONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KU...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents...

Page 4: ...st be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit inside its packaging while moving until reach ing the install...

Page 5: ...ual Installation manual Sealing material Small 35 150 Quantity 6 pcs Shape Model Min height above ceiling Air inlet panel Canvas connection for air inlet panel Color White FXSN20 25 32AV1 350mm or mor...

Page 6: ...shortened Indoor units should be installed as far away from fluorescent light ing as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight...

Page 7: ...the screws as shown in the drawing The paper pattern for installation is marked for 3 types of ceil ing openings Read the notations on the paper pattern care fully when installing 6 REFRIGERANT PIPIN...

Page 8: ...to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGER ANT PI...

Page 9: ...rainage flow during COOL running explained under TEST OPERATION WHEN ELECTRIC WIRING WORK IS NOT FINISHED Remove the electric parts box lid connect a power supply and remote controller to the terminal...

Page 10: ...wn below Be sure to adhere it to avoid water from outside unit CAUTION When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make ap...

Page 11: ...e of the sort could damage the entire system 7 Use only specified wire and tightly connect wires to termi nals Be careful wires do not place external stress on termi nals Keep wiring in neat order and...

Page 12: ...llowing table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation...

Page 13: ...11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid cryst...

Page 14: ...0901 FS HT 3P233622 5F EM08A072B...