English

5

(2) The fan speed for this indoor unit is preset to provide 

standard external static pressure.

• If higher or lower external static pressure is required, 

reposition the adapter for the PC board. Refer to “9. WIR-
ING EXAMPLE AND HOW TO SET THE REMOTE CON-
TROLLER”.

(3) Install the suspension bolts. (Use bolts of 10 mm diameter.) 

Use a hole-in-anchor, sunken insert, sunken anchor for 
existing ceilings, and a sunken insert, sunken anchor or 
other part to be procured in the field to reinforce the ceiling 
to bearing the weight of the unit.

5.

INDOOR UNIT INSTALLATION

〈〈

Installing optional accessories (except for the decoration 

panel) before installing the indoor unit is easier.

As for the parts to be used for installation work, be sure to use 
the provided accessories and specified parts designated by our 
company.

〉〉

(1) Install the indoor unit temporarily.

• Attach the hanger bracket to the suspension bolt. Be sure 

to fix it securely by using a nut and washer from the upper 
and lower sides of the hanger bracket.

(2) Check the unit is horizontally level.

CAUTION

The indoor unit is equipped with a built-in drain pump 
and float switch. At each of the unit

s 4 corners, verify 

that it is level by using a level or a water-filled vinyl tube. 
(If the unit is inclined against condensate flow, the float 
switch may malfunction and cause water to drip.)

(3) Tighten the upper nut.

(4) Fix the paper pattern for installation.

• The paper pattern for installation corresponds with the mea-

surements of the ceiling opening. Consult the builder for details.

• Attach the paper pattern for installation to the unit with the 

screws as shown in the drawing.
The paper pattern for installation is marked for 3 types of ceil-
ing openings. Read the notations on the paper pattern care-
fully when installing.

6.

REFRIGERANT PIPING WORK

Selection of Pipes

• Use the following type of refrigerant pipe.

Material: Phosphorus deoxidized seamless copper pipe 

(C1220T-1/2H or C1220T-H)

Pipe wall thickness: Product withstanding 12.3 MPa

Pipe wall thickness examples

(length : mm)

• Be sure to use pipes with clean outer and inner surfaces free 

of contaminants, such as sulfides, oxides, dust, chip, oil and 
fat, and moisture.
It is desirable that the adhesion oil in the piping system does 
not exceed 30 mg per 10 m.

• Be sure to conduct piping work within the maximum permis-

sible length, permissible difference in height, and permissible 
length after branching as shown in the following table.

• The refrigerant branching kit sold as an optional accessory is 

required for the branching of piping.
Select the kit according to the following table for the selection 
points of refrigerant branching kits.

For mounting air inlet panel directly

Model

A (mm)

FXSN20 · 25 · 32AV1

610

FXSN40 · 50AV1

760

FXSN63 · 100AV1

1460

Air inlet panel

350

or more

460

(Optional accessory)

Ceiling surface

Ceiling 
opening

A

(Ceiling opening)

Indoor unit
(Back side)

(length : mm)

180

Installation example

Note: All the above parts are field supplied.

Suspension bolt

Long nut or turn-buckle

Anchor

Indoor unit

Ceiling slab

Part to be procured in the field

[ Securing the hanger bracket ]

Washer (accessory)

Hanger bracket

Tighten
(double nut)

Pipe size 

(outer diameter)

Quality of material

Minimum wall 

thickness

φ 

6.4

1/2H

0.8

φ 

9.5

1/2H

1.0

φ 

12.7

1/2H

1.3

φ 

15.9

1/2H

1.8

Vinyl tube

Level

Screw for fixing the for 
paper pattern for installation 

(× 6 accessory)

Paper pattern for 
installation

01_EN_3P233622-5F.fm  Page 5  Thursday, December 18, 2008  4:21 PM

Summary of Contents for FXSN100AV1

Page 1: ...ONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KU...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents...

Page 4: ...st be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit inside its packaging while moving until reach ing the install...

Page 5: ...ual Installation manual Sealing material Small 35 150 Quantity 6 pcs Shape Model Min height above ceiling Air inlet panel Canvas connection for air inlet panel Color White FXSN20 25 32AV1 350mm or mor...

Page 6: ...shortened Indoor units should be installed as far away from fluorescent light ing as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight...

Page 7: ...the screws as shown in the drawing The paper pattern for installation is marked for 3 types of ceil ing openings Read the notations on the paper pattern care fully when installing 6 REFRIGERANT PIPIN...

Page 8: ...to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGER ANT PI...

Page 9: ...rainage flow during COOL running explained under TEST OPERATION WHEN ELECTRIC WIRING WORK IS NOT FINISHED Remove the electric parts box lid connect a power supply and remote controller to the terminal...

Page 10: ...wn below Be sure to adhere it to avoid water from outside unit CAUTION When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make ap...

Page 11: ...e of the sort could damage the entire system 7 Use only specified wire and tightly connect wires to termi nals Be careful wires do not place external stress on termi nals Keep wiring in neat order and...

Page 12: ...llowing table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation...

Page 13: ...11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid cryst...

Page 14: ...0901 FS HT 3P233622 5F EM08A072B...