background image

6

English

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.

(When using a heat pump, the temperature of the gas piping 

can reach up to approximately 120

°

C, 

so

 

use

 

insulation which 

is sufficiently resistant

.)

Also, in cases where the temperature and humidity of the 

refrigerant piping sections might exceed 30°C or RH80%, 
reinforce the refrigerant insulation. (20 mm or thicker) Con-
densation may form on the surface of the insulating mate-
rial.

Before refrigerant piping work, check which type of refrig-

erant is used. Proper operation is not possible if the types 
of refrigerant are not the same.

CAUTION

Use a pipe cutter for the type of refrigerant.

To prevent dust, moisture or other foreign matter from 
infiltrating the tube, either pinch the end or cover it with 
tape.

Do not allow anything other than the designated refrig-
erant to get mixed into the refrigerant circuit, such as air, 
etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away.

• The outdoor unit is charged with refrigerant.
• Check the pipe connector for gas leaks, then insulate it as 

shown in the drawing below.

• Wrap only the gas line side of the insulation for fitting (union) 

with the sealing pad.

Ventilate if refrigerant gas leaks while performing work.

• Connection of piping

It takes care of one’s health with the wet cloth so that part 
A should not exceed 80°C when the row is put.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting. (Fasten both ends with 
the clamps (accessory).) 

(Refer to Fig. 1)

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains flu-
orine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa (0.2 kg/cm

2

) with a pressure-

reducing valve if brazing while inserting nitrogen into the piping.

7.

DRAIN PIPING WORK

〈〈

Rig the drain pipe as shown below and take measures 

against condensation. Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.

〉〉

(1)

Carry out the drain piping
• The diameter of the drain pipe should be greater than or 

equal to the diameter of the connecting pipe (vinyl tube; 
pipe size: 25 mm; outer dimension: 32 mm).

• Keep the drain pipe short and sloping downwards at a gra-

dient of at least 1/100 to prevent air pockets from forming.

• If the drain hose cannot be sufficiently set on a slope, 

execute the drain raising piping.

• To keep the drain hose from sagging, space hanging 

wires every 1 to 1.5 m.

Field supply piping

Brazing

Part A

Indoor unit

Mid sealing pad
(accessory)

Gas pipe

Clamp

(× 4 accessory)

Insulation for fitting
(accessory)

(For gas pipe)

Fig. 1

Liquid pipe

Insulation for fitting
(accessory)

(For liquid pipe)

Refrigerant 
piping

Part to be 
brazed

Taping

Pressure-
reducing 
valve

hands valve

Nitrogen

Nitrogen

01_EN_3P233622-5F.fm  Page 6  Thursday, December 18, 2008  4:21 PM

Summary of Contents for FXSN100AV1

Page 1: ...ONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KU...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents...

Page 4: ...st be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit inside its packaging while moving until reach ing the install...

Page 5: ...ual Installation manual Sealing material Small 35 150 Quantity 6 pcs Shape Model Min height above ceiling Air inlet panel Canvas connection for air inlet panel Color White FXSN20 25 32AV1 350mm or mor...

Page 6: ...shortened Indoor units should be installed as far away from fluorescent light ing as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight...

Page 7: ...the screws as shown in the drawing The paper pattern for installation is marked for 3 types of ceil ing openings Read the notations on the paper pattern care fully when installing 6 REFRIGERANT PIPIN...

Page 8: ...to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGER ANT PI...

Page 9: ...rainage flow during COOL running explained under TEST OPERATION WHEN ELECTRIC WIRING WORK IS NOT FINISHED Remove the electric parts box lid connect a power supply and remote controller to the terminal...

Page 10: ...wn below Be sure to adhere it to avoid water from outside unit CAUTION When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make ap...

Page 11: ...e of the sort could damage the entire system 7 Use only specified wire and tightly connect wires to termi nals Be careful wires do not place external stress on termi nals Keep wiring in neat order and...

Page 12: ...llowing table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation...

Page 13: ...11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid cryst...

Page 14: ...0901 FS HT 3P233622 5F EM08A072B...

Reviews: