• In the upper space (including the back of the ceiling) of
the indoor unit where there is no possible dripping of
water from the refrigerant pipe, drain pipe, water pipe,
etc.
• If supporting structural members are not strong enough
to take the unit’s weight, the unit could fall out of place
and cause serious injury.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service
can be ensured.
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
CAUTION
• Install the indoor and outdoor units, power supply wiring and
connecting wires at least 1 meter away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient enough to eliminate the noise.)
• Install this unit where the height of bottom panel is more
than 2.5 m so that the user cannot easily touch.
[ PRECAUTION ]
If installing the wireless kit in a room with electronic fluores-
cent lighting (inverter or rapid start type), the remote con-
troller’s transmission distance may be shortened. Indoor
units should be installed as far away from fluorescent light-
ing as possible.
(2) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.
(Installation pitch is marked on the paper pattern for installation.
Refer to it to check for points requiring reinforcing.)
4.
PREPARATIONS BEFORE INSTALLA-
TION
(1) Relation of ceiling opening to unit and suspension bolt
position.
• For standard installation (air inlet on the bottom side),
choose one of the below two means of installation.
Note: For other than standard installation, contact your
Daikin dealer for details.
Maintenance
space
F
or installation
in high places
300 mm
or more
2500 mm
or more
Drain pipe
Liquid pipe
Power supply
wiring port
Maintenance drain hose
Transmission
wiring port
Gas pipe
Model
A (mm)
B (mm)
FXSN20 · 25 · 32AV1
550
600
FXSN40 · 50AV1
700
750
FXSN63 · 100AV1
1400
1450
For mounting air inlet panel with canvas connection
Model
A (mm)
FXSN20 · 25 · 32AV1
610
FXSN40 · 50AV1
760
FXSN63 · 100AV1
1460
B
A
Pipe
Suspension
bolt pitch
Indoor unit
800
Suspension bolt (× 4)
145
Suspension bolt pitch
630
(length : mm)
Air inlet panel
160
425
or more
(Optional accessory)
460
180
(160
-
300)
Ceiling
opening
Ceiling
surface
A
(Ceiling opening)
Indoor unit
(Back side)
Canvas
connection
for air inlet
panel
(Optional accessory)
(length : mm)
01_EN_3P233622-5F.fm Page 4 Thursday, December 18, 2008 4:21 PM