background image

16 Configuration

Installation and operation manual

19

FXSA15~140A2VEB
VRV system air conditioner
3P599602-1 – 2020.05

Setting: External static pressure

INFORMATION

▪ The fan speed of the indoor unit is preset to ensure the

standard external static pressure.

▪ To set a higher or lower external static pressure, reset

the initial setting with the user interface.

Settings for external static pressure can be achieved in 2 ways:

▪ Using the airflow automatic adjustment function

▪ Using the user interface

To set external static pressure by airflow automatic adjustment
function

NOTICE

▪ Do  NOT  adjust  the  dampers  during  the  fan  only

operation for airflow automatic adjustment.

▪ For the external static pressure higher than 100 Pa, do

NOT use airflow automatic adjustment function.

▪ If the ventilation paths have been changed, perform the

airflow automatic adjustment again.

▪ Test  run  MUST  be  done  with  a  dry  coil,  run  the  unit  for  2  hours

with fan only to dry the coil.

▪ Check  if  the  power  supply  wiring,  duct,  air  filter  are  properly

attached. If the closing damper is installed in the unit, make sure it
is open.

▪ If there is more than one air inlet and outlet, adjust the dampers so

that the airflow rate of each air inlet and outlet is conform with the
designed airflow rate.

1

Operate  the  unit  in  fan  only  mode  prior  to  using  the  airflow
automatic adjustment function.

2

Stop the air conditioning unit.

3

Set  the  value  number  “—“  to  03  for 

M

  11(21)  and 

SW

  7  and

continue according to the following table:

Setting content:

Then

(1)

M

SW

Airflow adjustment is OFF

11(21)

7

01

Press ON/OFF to return to normal operating
mode.

Possible consequence: 

The operation lamp

will light up and the unit will start the fan
operation for airflow automatic adjustment.

03

Operation stops after 1 to 8 minutes.

Possible consequence: 

Setting is finished

and the operation lamp will be off.

02

4

After airflow automatic adjustment is finished check if the value
number  “—“  is  set  to  02.  If  there  is  no  change,  perform  the
setting again.

To set external static pressure by the user interface

Check the indoor unit setting: the value number “—“ must be set to
01 for 

M

 11(21) and 

SW

 6.

1

Change  the  value  number  “—“  according  to  the  external  static
pressure of the duct to be connected as in table below.

External static pressure (Pa)

(1)

M

SW

Class

15~63

80+100

125+140

13(23)

6

01

30

40

50

02

03

30

04

40

40

05

50

50

50

06

60

60

60

07

70

70

70

08

80

80

80

09

90

90

90

10

100

100

100

11

110

110

110

12

120

120

120

13

130

130

130

14

140

140

140

15

150

150

150

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the air volume speed:

If you want…

Then

(1)

M

SW

During thermostat
OFF at cooling
operation

LL

(2)

12 (22)

6

01

Setup volume

(2)

02

OFF

(a)

03

Monitoring 1

(2)

04

Monitoring 2

(2)

05

During thermostat
OFF at heating
operation

LL

(2)

12 (22)

3

01

Setup volume

(2)

02

OFF

(a)

03

Monitoring 1

(2)

04

Monitoring 2

(2)

05

(a)

Only use in combination with optional remote sensor or when
setting 

M

 10 (20), 

SW 

2, —

 

3 is used.

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which 

"Time to clean filter"

 notification

is displayed on the user interface.

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

SW

: Setting number

• —: Value number

: Default

(2)

Fan speed:

LL

: Low fan speed (set during thermostat OFF)

L

: Low fan speed (set by the user interface)

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user

interface.

Monitoring 1, 2

: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by 

LL

 (Monitoring 1) or by 

L

(Monitoring 2).

Summary of Contents for FXSA15A2VEB

Page 1: ...l VRV system air conditioner English Installation and operation manual VRV system air conditioner FXSA15A2VEB FXSA20A2VEB FXSA25A2VEB FXSA32A2VEB FXSA40A2VEB FXSA50A2VEB FXSA63A2VEB FXSA80A2VEB FXSA10...

Page 2: ...document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na...

Page 3: ...un 18 16 Configuration 18 16 1 Field setting 18 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document INFORMATION Make s...

Page 4: ...se booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 418 Refrigerant piping installation see 13 Piping installation 416 CAUTION Do NOT use m...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...for your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...r or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the u...

Page 8: ...neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be dama...

Page 9: ...e check the unit stand and fitting for damage If damaged the unit may fall and result in injury NOTICE Do NOT wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel...

Page 10: ...erate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable b...

Page 11: ...terface displays Notify your installer and report the error code To display an error code see the reference guide of the user interface If the system does NOT operate properly except for the above men...

Page 12: ...nstallation options c a b 1100 b 1100 A B c c d e f mm g 125 b 800 160 160 300 245 h 460 C f g a a A Standard rear suction B Installation with rear canvas duct and duct service opening C Installation...

Page 13: ...d the float switch might malfunction and cause water to drip 12 2 2 Guidelines when installing the ducting WARNING Do NOT install operating ignition sources example open flames an operating gas applia...

Page 14: ...diameter Slope Make sure the drain piping slopes down at least 1 100 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensat...

Page 15: ...llation of the system is not yet completed 1 Temporarily connect electrical wiring Remove the service cover c Connect the power supply a Connect the user interface b Reattach the service cover L N c a...

Page 16: ...1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness...

Page 17: ...g separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line...

Page 18: ...n the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor a...

Page 19: ...will be off 02 4 After airflow automatic adjustment is finished check if the value number is set to 02 If there is no change perform the setting again To set external static pressure by the user inter...

Page 20: ...Depending on the needs of the user you may disable enable the automatic restart after a power failure If you want auto restart after power failure Then 1 M SW Disabled 12 22 5 01 Enabled 02 17 Technic...

Page 21: ...PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T...

Page 22: ......

Page 23: ......

Page 24: ...3P599602 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: