12 Unit installation

Installation and operation manual

13

FXSA15~140A2VEB
VRV system air conditioner
3P599602-1 – 2020.05

a

a

b

a

Air filter holding plate with air filter(s)

b

Interchangeable plate

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

b

a

c

e

d

a

Anchor

b

Ceiling slab

c

Long nut or turnbuckle

d

Suspension bolt

e

Indoor unit

Suspension  bolts.

  Use  M10  suspension  bolts  for  installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

e:

 630

e: A

(mm)

a

b

b

d

c

a

Nut (field supply)

b

Washer (accessories)

c

Hanger bracket

d

Double nut (field supply)

e

Suspension bolt pitch

Class

A (mm)

15~32

588

40~50

738

63~80

1038

100~125

1438

Class

A (mm)

140

1588

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Water level

b

Vinyl tube

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

12.2.2

Guidelines when installing the ducting

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16.1 Field setting" 

[

4

 18]).

The ducting is to be field supplied.

1

Connect the canvas duct to the inside of the flange on both inlet
and outlet side. For connecting the canvas duct, use accessory
screws.

2

Connect the duct to the canvas duct.

a

b

c

b

a

f

f

e

e

d

d

a

Screws for duct flanges (accessory)

b

Flange (located on the unit)

c

Indoor unit

d

Insulation (field supply)

Summary of Contents for FXSA15A2VEB

Page 1: ...l VRV system air conditioner English Installation and operation manual VRV system air conditioner FXSA15A2VEB FXSA20A2VEB FXSA25A2VEB FXSA32A2VEB FXSA40A2VEB FXSA50A2VEB FXSA63A2VEB FXSA80A2VEB FXSA10...

Page 2: ...document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na...

Page 3: ...un 18 16 Configuration 18 16 1 Field setting 18 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document INFORMATION Make s...

Page 4: ...se booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 418 Refrigerant piping installation see 13 Piping installation 416 CAUTION Do NOT use m...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...for your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...r or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the u...

Page 8: ...neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be dama...

Page 9: ...e check the unit stand and fitting for damage If damaged the unit may fall and result in injury NOTICE Do NOT wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel...

Page 10: ...erate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable b...

Page 11: ...terface displays Notify your installer and report the error code To display an error code see the reference guide of the user interface If the system does NOT operate properly except for the above men...

Page 12: ...nstallation options c a b 1100 b 1100 A B c c d e f mm g 125 b 800 160 160 300 245 h 460 C f g a a A Standard rear suction B Installation with rear canvas duct and duct service opening C Installation...

Page 13: ...d the float switch might malfunction and cause water to drip 12 2 2 Guidelines when installing the ducting WARNING Do NOT install operating ignition sources example open flames an operating gas applia...

Page 14: ...diameter Slope Make sure the drain piping slopes down at least 1 100 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensat...

Page 15: ...llation of the system is not yet completed 1 Temporarily connect electrical wiring Remove the service cover c Connect the power supply a Connect the user interface b Reattach the service cover L N c a...

Page 16: ...1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness...

Page 17: ...g separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line...

Page 18: ...n the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor a...

Page 19: ...will be off 02 4 After airflow automatic adjustment is finished check if the value number is set to 02 If there is no change perform the setting again To set external static pressure by the user inter...

Page 20: ...Depending on the needs of the user you may disable enable the automatic restart after a power failure If you want auto restart after power failure Then 1 M SW Disabled 12 22 5 01 Enabled 02 17 Technic...

Page 21: ...PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T...

Page 22: ......

Page 23: ......

Page 24: ...3P599602 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: