![background image](http://html1.mh-extra.com/html/daikin/fxsa15a2veb/fxsa15a2veb_installation-and-operation-manual_4700774015.webp)
12 Unit installation
Installation and operation manual
15
FXSA15~140A2VEB
VRV system air conditioner
3P599602-1 – 2020.05
≤4 mm
A-A'
b
a
d
c
3
1
2~6
1
4
d
A
A'
A
A'
e
5
2
c
b
a
a
Drain pipe connection (attached to the unit)
b
Drain hose (accessory)
c
Metal clamp (accessory)
d
Large sealing pad (accessory)
e
Drain piping (field supply)
NOTICE
▪ Do NOT remove the drain pipe plug. Water might leak
out.
▪ Use the drain outlet only to discharge the water before
maintenance.
▪ Insert and remove the drain plug gently. Excessive
force may deform the drain socket of the drain pan.
Pull out the plug.
▪ Do NOT wiggle the plug up and down.
a
Push in the plug.
▪ Set the plug and push it in using a Phillips screwdriver.
a
b
a
Drain plug
b
Philips screwdriver
To check for water leaks
The procedure differs depending on whether installation of the
system is already completed. When installation of the system is not
yet completed, temporarily connect the user interface and power
supply to the unit.
When installation of the system is not yet completed
1
Temporarily connect electrical wiring.
▪ Remove the service cover (c).
▪ Connect the power supply (a).
▪ Connect the user interface (b).
▪ Reattach the service cover.
L
N
c
a
b
a
Power supply terminal block
b
User interface terminal block
c
Service cover with wiring diagram
2
Turn ON the power supply.
3
Start fan only operation (see the reference guide or the service
manual of the user interface).
4
Remove the water inlet cover (1 screw).
5
Gradually pour approximately 1 l of water through the water
inlet, and check for leaks.
f
b
e
d
c
a
a
Water inlet
b
Portable pump
c
Water inlet cover
d
Bucket (adding water through water inlet)
e
Drain outlet for maintenance
f
Refrigerant pipes
6
Turn OFF the power.
7
Disconnect the electrical wiring.
▪ Remove the service cover.
▪ Disconnect the power supply.
▪ Disconnect the user interface.
▪ Reattach the service cover.
When installation of the system is already completed
1
Start cooling operation (see the reference guide or the service
manual of the user interface).
2
Gradually pour approximately 1 l of water through the water
inlet, and check for leaks (see