background image

15 Commissioning

Installation and operation manual

18

FXSA15~140A2VEB

VRV system air conditioner

3P599602-1 – 2020.05

CAUTION

▪ Each  indoor  unit  has  to  be  connected  to  a  separate

user interface. Only a safety system compatible remote
controller  can  be  used  as  the  user  interface.  See
technical  data  sheet  for  remote  controller  compatibility
(e.g. BRC1H52/82*).

▪ The  user  interface  has  to  be  put  in  the  same  room  as

the  indoor  unit.  For  details,  please  refer  to  the
installation and operation manual of the user interface.

15

Commissioning

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

15.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  and  operation
instructions,  as  described  in  the 

installer  and  user

reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

Make  sure 

drain  piping

  is  properly  installed,  insulated

and drainage flows smoothly. Check for water leaks.

Possible consequence: 

Condensate water might drip.

The 

ducting

 is properly installed and insulated.

The 

refrigerant  pipes

  (gas  and  liquid)  are  installed

correctly and thermally insulated.

There are NO 

refrigerant leaks

.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

15.2

To perform a test run

INFORMATION

▪ Perform the test run according to the instructions in the

outdoor unit manual.

▪ The test run is only completed if there is no malfunction

code displayed on the user interface or the outdoor unit
7‑segment display.

▪ See  the  service  manual  for  the  complete  list  of  error

codes and a detailed troubleshooting guideline for each
error.

NOTICE

Do NOT interrupt the test run.

16

Configuration

16.1

Field setting

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Ceiling height

▪ Bottom suction or rear suction installation

▪ External static pressure setting using:

▪ Airflow automatic adjustment setting

▪ User interface

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

▪ Thermostat sensor selection

▪ Thermostat differential changeover (if remote sensor is used)

▪ Differential for automatic changeover

▪ Auto-restart after power failure

Setting: Ceiling height

This  setting  must  correspond  with  the  actual  distance  to  the  floor,
capacity class and air flow directions.

If the distance to the floor is (m)

Then

(1)

M

SW

≤2.7

13 (23)

0

01

2.7<x≤3.0

02

3.0<x≤3.5

03

Setting: Bottom suction or rear suction installation

This  setting  must  correspond  with  the  installation  type:  rear  suction
(default) or bottom suction.

If you have the installation

with…

Then

(1)

M

SW

Rear suction

13(23)

11

01

Bottom suction

02

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

SW

: Setting number

• —: Value number

: Default

Summary of Contents for FXSA15A2VEB

Page 1: ...l VRV system air conditioner English Installation and operation manual VRV system air conditioner FXSA15A2VEB FXSA20A2VEB FXSA25A2VEB FXSA32A2VEB FXSA40A2VEB FXSA50A2VEB FXSA63A2VEB FXSA80A2VEB FXSA10...

Page 2: ...document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na...

Page 3: ...un 18 16 Configuration 18 16 1 Field setting 18 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document INFORMATION Make s...

Page 4: ...se booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 418 Refrigerant piping installation see 13 Piping installation 416 CAUTION Do NOT use m...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...for your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...r or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the u...

Page 8: ...neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be dama...

Page 9: ...e check the unit stand and fitting for damage If damaged the unit may fall and result in injury NOTICE Do NOT wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel...

Page 10: ...erate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable b...

Page 11: ...terface displays Notify your installer and report the error code To display an error code see the reference guide of the user interface If the system does NOT operate properly except for the above men...

Page 12: ...nstallation options c a b 1100 b 1100 A B c c d e f mm g 125 b 800 160 160 300 245 h 460 C f g a a A Standard rear suction B Installation with rear canvas duct and duct service opening C Installation...

Page 13: ...d the float switch might malfunction and cause water to drip 12 2 2 Guidelines when installing the ducting WARNING Do NOT install operating ignition sources example open flames an operating gas applia...

Page 14: ...diameter Slope Make sure the drain piping slopes down at least 1 100 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensat...

Page 15: ...llation of the system is not yet completed 1 Temporarily connect electrical wiring Remove the service cover c Connect the power supply a Connect the user interface b Reattach the service cover L N c a...

Page 16: ...1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness...

Page 17: ...g separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line...

Page 18: ...n the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor a...

Page 19: ...will be off 02 4 After airflow automatic adjustment is finished check if the value number is set to 02 If there is no change perform the setting again To set external static pressure by the user inter...

Page 20: ...Depending on the needs of the user you may disable enable the automatic restart after a power failure If you want auto restart after power failure Then 1 M SW Disabled 12 22 5 01 Enabled 02 17 Technic...

Page 21: ...PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T...

Page 22: ......

Page 23: ......

Page 24: ...3P599602 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: