12 Unit installation
Installation and operation manual
14
FXSA15~140A2VEB
VRV system air conditioner
3P599602-1 – 2020.05
e
Canvas duct (field supply)
f
Aluminium tape (field supply)
▪
Fixing screws
. When installing an air inlet duct, select fixing
screws that stick out 5 mm on the inside of the flange to protect
the air filter from damage during maintenance of the filter.
a
b
c
5 mm
a
Air inlet duct
b
Inside of the flange
c
Fixing screw
3
Wind aluminium tape around the flange and duct connection.
Make sure there are no air leaks at any other connection.
4
Insulate the duct to prevent condensation from forming. Use
glass wool or polyethylene foam 25 mm thick.
▪
Filter.
Be sure to attach an air filter inside the air passage on the
intake side. Use an air filter with dust collecting efficiency ≥50%
(gravimetric method).
12.2.3
Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪
Pipe length.
Keep drain piping as short as possible.
▪
Pipe size.
Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 20 mm nominal diameter and
26 mm outer diameter).
▪
Slope.
Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
1~1.5 m
a
a
Hanging bar
O
Allowed
X
Not allowed
▪
Condensation.
Take measures against condensation. Insulate
the complete drain piping in the building.
▪
Rising piping
. If necessary to make the slope possible, you can
install rising piping.
▪ Drain hose inclination: 0~75 mm to avoid stress on the piping
and to avoid air bubbles.
≤625
≤300
0~75
1000~1500
(mm)
b
a
b
a
d
d
c
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe nominal Ø20 mm and outer
Ø26 mm)
d
Hanging bars (field supply)
▪
Combining drain pipes.
You can combine drain pipes. Make
sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.
≥100
≤625
(mm)
a
a
T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
a
Drain outlet for maintenance
b
Refrigerant pipes
c
Drain pipe connection
1
Push the drain hose as far as possible over the drain pipe
connection.
2
Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.
3
Check for water leaks (see
15]).
4
Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with tie wraps.
5
Connect the drain piping to the drain hose.