CAUTION

Keep in mind that a shortage of airflow quantity or water leakage 
will result because the air conditioner will be operated outside 
the rated range of airflow quantity if the external static pressure 
is wrongly set.

3. Filter Sign Settings

• The remote controller is provided with an LCD that tells 

the time of air filter cleaning.

• If the air conditioner is used in places with excessive dust, 

change the “SECOND CODE NO.” as shown in Table 6. 
The “SECOND CODE NO.” is set to 01 (standard) at fac-
tory set.

Table 6

* Select “No display” under conditions in which the cleaning 
display is not required, such as the time of regular mainte-
nance.

12. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when 

an malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An expla-
nation of malfunction codes and the corresponding trouble is 
provided in “CAUTION FOR SERVICING” of the outdoor unit.
If any of the items in Table 8 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 7

Table 8

CAUTION

If interior finish work is continuing on completion of the test 
operation of the air conditioner, explain the customer not to 
operate the air conditioner until the interior finish work is com-
pleted for the protection of the air conditioner. 
Otherwise, substances that will be generated from interior finish 
work materials, such as paint and adhesive agents, may con-
taminate the air conditioner.

External Static 

Pressure

MODE NO.

FIRST 

CODE NO.

SECOND 

CODE NO.

30Pa (*1)(*4)

13 (23)

06

01

50Pa

02

60Pa

03

70Pa

04

80Pa

05

90Pa

06

100Pa

07

110Pa (*3)

08

120Pa (*3)

09

130Pa (*3)

10

140Pa (*3)

11

150Pa (*3)(*4)

12

160Pa (*3)(*4)

13

180Pa 
(*2)(*3)(*4)

14

200Pa 
(*2)(*3)(*4)

15

Dirt

Time for 

display

MODE 

NO.

FIRST 
CODE 

NO.

SECOND 

CODE 

NO.

Standard

Approxi-

mately 2500 

hours

10 (20)

0

01

Excessive 

dust

Approxi-

mately 1250 

hours

02

No display (*)

3

Remote controller display

Contents

“A8” lit

Error in power supply voltage to 
indoor unit.

“C1” lit

Fan driver PCB of indoor unit 

 

indoor control PCB transmission 
error.

“C6” lit

Improper combination of fan driver 
PCB of indoor unit or setting failure 
in control PCB type.

“U3” lit

Test operation of outdoor unit has 
not been finished.

Remote control display

Content

” is lit up

• There is a short circuit at the 

FORCED OFF terminals (T1, T2)

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is 

off.

• The outdoor unit has not been 

wired for power supply.

• Incorrect wiring for the transmis-

sion wiring and / or FORCED OFF 
wiring.

No display

• The power on the indoor unit is 

off.

• The indoor unit has not been 

wired for power supply.

• Incorrect wiring for the remote 

controller wiring, the transmission 
wiring and / or the FORCED OFF 
wiring.

01_EN_3PN06583-7N.fm  Page 14  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ100PVE

Page 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Page 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Page 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Page 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Page 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Page 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Page 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Page 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Page 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Page 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Page 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Page 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Page 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Page 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Page 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Page 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Page 17: ... 0904 HT 3PN06583 7N EM07A049D ...

Reviews: