background image

English

3

2-3

OPTIONAL ACCESSORIES

• These are two types of remote controllers: wired and wire-

less. Select a remote controller according to customer 
request and install in an appropriate place.

Table 1

NOTE

• If you wish to use a remote controller that is not listed in 

Table 1, select a suitable remote controller after consulting 
catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL 
CARE DURING CONSTRUCTION AND CHECK 
AFTER INSTALLATION IS FINISHED.

a. Items to be checked after completion of work

Also review the “SAFETY PRECAUTIONS”.

b. Items to be checked at time of delivery

c. Points for explanation about operations

2-4

NOTE TO INSTALLER

• Be sure to instruct customers how to properly operate the 

unit (especially cleaning filters, operating different functions, 
and adjusting the temperature) by having them carry out 
operations themselves while looking at the manual.

3.

SELECTING INSTALLATION SITE

Hold the hanging brackets in the case of moving the 

indoor and outdoor units at the time of and after opening 
the packages. Do not impose undue force on other parts, 
such as the refrigerant piping, drain piping, or flanges, in 
particular.

〉 

Add heat insulation material to the indoor unit if the tem-

perature above the ceiling is likely to exceed 30°C and a rel-
ative humidity of 80%.

〉 

Make sure that the insulation material is made of glass wool 

or polyethylene foam, has a minimum thickness of 10 mm, 
and can be accommodated in the opening on the ceiling.

〉 

(1) Select an installation site where the following conditions are 

fulfilled and that meets with your customer’s approval.

• A place where cool (warm) air is delivered to the entire 

room.

• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• If supporting structural members are not strong enough 

to take the unit’s weight, the unit could fall out of place 
abd cause serious injury.

• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service 

can be ensured. 

(Refer to Fig. 2-1)

• Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation 
manual of the outdoor unit.)

CAUTION

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 1 meter away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient enough to eliminate the noise.)

Name

Washer (11)

Wire fixing 

bracket (12)

Wire fixing 
screw (13)

(Other)

• Operation 

manual

• Installation 

manual

Quantity

8 pcs.

2 pcs.

2 pcs.

Shape

Remote controller

Wired type

Wireless type

Heat pump type

Cooling only type

Items to be checked

If not properly done, what is 
likely to occur.

Check

Are the indoor and outdoor 
unit fixed firmly?

The units may drop, vibrate 
or make noise.

Was the installation of the 
outdoor unit completed?

The unit may malfunction or 
the components burn out.

Is the gas leak test 
finished? 

No cooling or heating.

Is the unit fully insulated? 
(Refrigerant piping, drain 
piping, and duct)

Condensate water may drip.

Dose drainage flow 
smoothly?

Condensate water may drip.

Does the power supply volt-
age conform to the indica-
tion on the name plate?

The unit may malfunction or 
the components burn out.

Are wiring and piping 
correct?

The unit may malfunction or 
the components burn out.

Is the air conditioner prop-
erly grounded?

Dangerous in case of cur-
rent leakage.

Is wiring size according to 
specifications?

The unit may malfunction or 
the components burn out.

Is something blocking the 
air outlet or inlet of either 
the indoor or outdoor units?

No cooling or heating.

Did you set the external 
static pressure? 

No cooling or heating.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in 
the system is not clear.

Did you check that no wiring 
connection screws were 
loose?

Electric shock or fire.

M4×8

Items to be checked

Check

Are you sure the control box lid, air filter, air inlet grille, and 
air outlet grille are mounted?

Did you explain about operations while showing the opera-
tion manual to your customer?

Did you deliver the operation manual along with the instal-
lation manual to the customer?

Did you explain the customer the handling and cleaning 
methods of the field supplies (e.g., the air filter, air inlet 
grilles, and air outlet grille)?

Did you deliver instruction manual, if any, for the field sup-
plies to the customer?

The items with 

WARNING and 

CAUTION marks in the opera-

tion manual are the items pertaining to possibilities for bodily injury 
and material damage in addition to the general usage of
the product. Accordingly, it is necessary that you make a full expla-
nation about the described contents and also ask your customers to 
read the operation manual.

01_EN_3PN06583-7N.fm  Page 3  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ100PVE

Page 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Page 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Page 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Page 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Page 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Page 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Page 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Page 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Page 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Page 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Page 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Page 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Page 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Page 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Page 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Page 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Page 17: ... 0904 HT 3PN06583 7N EM07A049D ...