VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1

2. BEFORE INSTALLATION ................................................ 2

3. SELECTING INSTALLATION SITE ................................. 3

4. PREPARATIONS BEFORE INSTALLATION.................... 4

5. INDOOR UNIT INSTALLATION ....................................... 5

6. REFRIGERANT PIPING WORK ..................................... 5

7. DRAIN PIPING WORK .................................................... 7

8. DUCT WORK .................................................................. 8

9. ELECTRIC WIRING WORK ............................................ 9

10. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER...................................... 10

11. FIELD SETTING............................................................ 12

12. TEST OPERATION........................................................ 14

1.

SAFETY PRECAUTIONS

Please read these “SAFETY PRECAUTIONS” carefully before 
installing air conditioning unit and be sure to install it correctly.
After completing installation, conduct a trial operation to check 
for faults and explain to the customer how to operate the air con-
ditioner and take care of it with the aid of the operation manual. 
Ask the customer to store the installation manual along with the 
operation manual for future reference.

This air conditioner comes under the term “appliances not 
accessible to the general public”.

Safety Precaution

This unit is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

Meaning of WARNING and CAUTION notices

WARNING

 ............. Failure to follow these instructions 

properly may result in personal injury 
or loss of life.

CAUTION

  ..............Failure to observe these instructions 

properly may result in property dam-
age or personal injury, which may be 
serious depending on the circum-
stances.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work.
Do not attempt to install the air conditioner yourself. Improper 
installation may result in water leakage, electric shocks or 
fire.

• Install the air conditioner in accordance with the instructions 

in this installation manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage. When the air conditioner is to be 
installed in a small room, it is necessary to take proper mea-
sures so that the amount of any leaked refrigerant does not 
exceed the concentration limit in the event of a leakage. 
Otherwise, this may lead to an accident due to oxygen deple-
tion.

• Be sure to use only the specified accessories and parts for 

installation work.
Failure to use the specified parts may result in the unit falling, 
water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit.
A foundation of insufficient strength may result in the equip-
ment falling and causing injury.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit 
falling and causing accidents.

• Make sure that a separate power supply circuit is provided for 

this unit and that all electrical work is carried out by qualified 
personnel according to local laws and regulations and this 
installation manual.
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are 

used, and that there is no strain on the terminal connections 
or wires.
Improper connections or securing of wires may result in 
abnormal heat build-up or fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in elec-
tric shocks, fire or the terminals overheating.

• If refrigerant gas leaks during installation, ventilate the area 

immediately.
Toxic gas may be produced if the refrigerant comes into con-
tact with fire.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the 
room and comes into contact with a source of fire, such as a 
fan heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical 

parts.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or 
telephone earth lead. Imperfect earthing may result in elec-
tric shocks or fire.
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping to ensure proper drainage and insulate 
piping to prevent condensation.
Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor and outdoor units, power cord and connect-

ing wires at least 1 meter away from televisions or radios to 
prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 
1 meter may not be sufficient to eliminate noise.)

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as 
possible.

01_EN_3PN06583-7N.fm  Page 1  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ100PVE

Page 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Page 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Page 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Page 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Page 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Page 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Page 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Page 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Page 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Page 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Page 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Page 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Page 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Page 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Page 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Page 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Page 17: ... 0904 HT 3PN06583 7N EM07A049D ...