background image

4

English

• In the case of the installation of a wireless remote controller, 

the transmission distance of the wireless remote controller may 
be shortened if the room has a fluorescent light of electronic 
lighting type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent 
light as far as possible.

(2) Use hanging bolts to install the indoor unit. Check that the 

place of installation withstands the weight of the indoor unit. 
Secure the hanging bolts with proper beams if necessary.

4.

PREPARATIONS BEFORE INSTALLATION

(1) Check the positional relationship between the ceiling open-

ing hole and the hanging bolt of the unit.

• For the maintenance, inspection, and other servicing 

purposes of the control box and drain pump, prepare one 
of the following service spaces.
1. Inspection hatch 1 (450 × 450) for the control box and 

a minimum space of 300 mm for the lower part of the 
product. 

(Refer to Fig. 2-2)

2. Inspection hatch 1 (450 × 450) for the control box and 

inspection hatch 2 for the lower part of the product 
(see axial direction view A-1). 

(Refer to Fig. 2-3)

3. Inspection hatch 3 for the lower part of the product 

and the lower part of the control box (see axial direc-
tion view A-2). 

(Refer to Fig. 2-3)

(2) Mount the canvas ducts to the air outlet and inlet so that the 

vibration of the air conditioner will not be transmitted to the 
duct or ceiling. Apply a sound-absorbing material (insula-
tion material) to the inner wall of the duct and vibration insu-
lation rubber to the hanging bolts (refer to 

8. DUCT WORK

).

(3) Open installation holes (if the ceiling already exists).

• Open the installation holes on the ceiling. Lay the refrig-

erant piping, drain piping, power line, transmission wir-
ing, and remote controller wiring for the piping and wiring 
connection port of the unit.
In the case of the installation of a wireless remote con-
troller, refer to the installation manual provided with the 
wireless remote controller.
Refer to 

6. REFRIGERANT PIPING WORK

7. DRAIN 

PIPING WORK

, and 

10. WIRING EXAMPLE AND HOW 

TO SET THE REMOTE CONTROLLER

.

• The ceiling framework may need reinforcement in order 

to keep the ceiling horizontal and prevent the vibration of 
the ceiling after the installation holes are opened. For 
details, consult your construction or interior contractor.

(4) Install the hanging bolts. Make sure that the hanging bolts 

are M10 in size.

• Use hole-in anchors if the hanging bolts already exist; 

otherwise use embedded inserts and embedded founda-
tion bolts so that they will withstand the weight of the unit. 
Adjust the distance to the ceiling surface in advance.

(length: mm)

Ceiling

Floor surface

• The H1 dimension indicates the 

height of the product.

• Determine the H2 dimension by 

maintaining a downward slope of 
at least 1/100 as specified in 
“7. DRAIN PIPING WORK”.

Min. 20

Min. 300

Min. 450

Min. 2500

Min. 700 (service space)

(If no ceiling board is provided.)

*H1=300

*H2=Min. 620

[Required installation place]

The dimensions indicate the 
minimum required space of 
installation.

Fig. 2-1

700

631

(Hanging bolt pitch)

Inspection hatch 1 
(450×450)

Inspection hatch

Control box

Control box

Ceiling

B

C

(Hanging bolt pitch)

Bottom of unit

Air inlet

Air outlet

Hanging bolt (× 4)

*H3=Min. 300

Fig. 2-2

Case 1

700

700

Inspection hatch

Inspection hatch 1 
(450×450)

Inspection 
hatch 2

Inspection hatch 3

(Same as the indoor 
unit size +300 or more)

Control box

Control box

Control box

Inspection hatch

(Ceiling opening)

Ceiling

Axial direction view A-1

Axial direction view A-2

Min. D=B+300

Min. 200

B

*H3=Min. 20

20 • 25 • 32 type

550

588

850

Model

B

C

D

700

738 1000

1000 1038 1300

1400 1438 1700

40 type

50 • 63 • 80 type

100 • 125 • 140 type

(length: mm)

A

Fig. 2-3

Case 2, 3

(Same as the 
indoor unit 
size or more)

• Determine the H3 

dimension by maintaining a 
downward slope of at least 
1/100 as specified in 
“7. DRAIN PIPING WORK”.

Note)   All the above parts are field supplied. 

Installation example

Ceiling slab

Anchor

Long nut or turn-buckle

Hanging bolt

Indoor unit

01_EN_3PN06583-7N.fm  Page 4  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ100PVE

Page 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Page 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Page 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Page 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Page 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Page 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Page 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Page 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Page 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Page 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Page 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Page 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Page 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Page 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Page 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Page 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Page 17: ... 0904 HT 3PN06583 7N EM07A049D ...

Reviews: