background image

English

5

5.

INDOOR UNIT INSTALLATION

It may be easier to install accessories (sold separately) 

before installing the indoor unit. Refer to the installation 
manuals provided to the accessories as well.

〉 

Be sure to use the accessories and specified parts for 
installation work.

(1) Temporally install the indoor unit.

• Connect the hanging brackets to the hanging bolts. Be 

sure to use and tighten the nut and washer (11) for each 
hanging bracket from both upper and lower sides of the 
hanging bracket. 

(Refer to Fig. 3)

 At that time, the fall of 

the washer (11) for the hanging bracket can be pre-
vented if the washing fixing plate (9) is used.

CAUTION

During the installation work, perform the curing of the air 
outlet and protect the resin drain pan of the indoor unit 
from the intrusion of foreign substances, such as weld-
ing spatters.

Otherwise, water leakage may occur as a result of damage, 
such as hole damage, to the resin drain pan.

(2) Make adjustments so that the unit will be in the right posi-

tion.

(3) Check the level of the unit.
(4) Remove the washer fixing plates for the falling prevention of 

the washers for the hanging brackets, tighten the nuts on 
the upper side, and securely fix the unit.

CAUTION

• Use the level and check that the unit is installed horizontally.

(4-directions)

• In the case of using a vinyl tube in place of the level, put the 

both edges of the vinyl tube in close contact with the bottom 
of the product to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set 
high, in particular, the float switch will not operate normally 
and water leakage may result.

6.

REFRIGERANT PIPING WORK

As for the refrigerant piping of the outdoor unit, refer to the 

installation manual provided to the outdoor unit.

〉 

Perform heat insulation work on both gas piping and liquid 

piping, or otherwise water leakage may result.

〉 

Use the insulation material that withstands a temperature 

of 120°C.

〉 

Reinforce the insulation material for the refrigerant piping if 

the ambient temperature is high, or otherwise dew conden-
sation may result on the surface of the insulation material.

〉 

Make sure that the refrigerant is R410A before refrigerant 

piping work. If the refrigerant is different, the air condi-
tioner will not operate normally.

〉 

CAUTION

This product uses new refrigerant (R410A) only. Be sure to 
keep the items on the right-hand side and conduct the 
installation work.

Use a dedicated pipe cutter and flare tool for R410A.

When connecting the flare, apply ether oil or ester oil 
only to inner side of the flare.

Be sure to use the flare nut provided with the unit. (Do 
not use a different flare nut (such as a type-1 flare nut), 
or otherwise refrigerant leakage may result.)

Perform the curing of the piping with pinching or taping 
of the piping in order to prevent the intrusion of dirt, 
dust, and moisture into the piping.

CAUTION

Be sure to use the specified type of refrigerant for the 
refrigeration cycle and do not contaminate the refriger-
ant with air.

Ventilate the room in case of refrigerant leakage during 
installation work.

(1) Connect the piping.

• The outdoor unit is filled with refrigerant.
• When connecting or disconnecting piping to or from the 

unit, 

be sure to use two spanners and two torque 

wrenches. (Refer to Fig. 4)

Washer (11) (accessory)

Part to be procured in the field

Washer fixing plate (9) 
(accessory)

Insert

Tighten from above and below 
(Double nut)

[Fixing hanging brackets]

[Fixing method of washers]

Fig. 3

Nut on the upper side

Hanging bracket

Bottom of product

Level

Vinyl tube

Torque wrench

Spanner

Piping union

Flare nut

Fig. 4

01_EN_3PN06583-7N.fm  Page 5  Saturday, February 28, 2009  3:02 PM

Summary of Contents for FXMQ100PVE

Page 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Page 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Page 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Page 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Page 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Page 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Page 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Page 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Page 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Page 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Page 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Page 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Page 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Page 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Page 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Page 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Page 17: ... 0904 HT 3PN06583 7N EM07A049D ...

Reviews: