background image

English

5

6. REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

〉 

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.

(When using a heat pump, the temperature of the gas piping 
can reach up to approximately 120°C, so use insulation which is 
sufficiently resistant.)

Also, in cases where the temperature and humidity of the 

refrigerant piping sections might exceed 30°C or RH80%, 
reinforce the refrigerant insulation. (20 mm or thicker) Con-
densation may form on the surface of the insulating material.

〉 

Before refrigerant piping work, check which type of refrig-

erant is used. Proper operation is not possible if the types 
of refrigerant are not the same.

CAUTION

Use a pipe cutter and flare suitable for the type of refrig-
erant.

Apply ester oil or ether oil around the flare portions 
before connecting.

To prevent dust, moisture or other foreign matter from 
infiltrating the tube, either pinch the end or cover it with 
tape.

Do not allow anything other than the designated refrig-
erant to get mixed into the refrigerant circuit, such as air, 
etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away.

• The outdoor unit is charged with refrigerant.
• Be sure to use both a spanner and torque wrench together, 

as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit.

• To prevent flare nut cracking and gas leaks, be sure to use 

both a spanner and torque wrench together, as shown in the 
drawing below, when connecting or disconnecting pipes to/
from the unit.

• Refer to the Table 2 for the dimensions of flare nut spaces.
• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or  
four times first, then screw in.

• Refer to the Table 2 for tightening torque. 
• Ventilate if refrigerant gas leaks while performing work.

Table 2

NOTE

The flare nuts used must be those included with the 
main body.

CAUTION

Over-tightening may damage the flare and cause a refriger-
ant leakage.

Use “ Table 3 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Table 3 ”.

• After checking the pipe-connection for gas leakage, be sure 

to insulate the liquid and gas piping, referring to the figure 
below.

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

NOTE

• Attached piping is needed for connecting gas piping of 

FXMQ200 · 250M(A)VE, MAV7. Use attached piping accord-
ing to the size of the piping to be connected.
When connecting the included piping, use the included pip-
ing flange hex bolts (2) and spring washers (2).

• Connect refrigerant piping and branching according to the 

attached installation manuals that come with the outdoor 
unit.

Pipe 

size

Tightening torque

Flare 

dimensions

A (mm)

Flare shape

 φ

 6.4

(1/4”)

14.2 – 17.2N·m

8.7 – 9.1

 φ

 9.5

(3/8”)

32.7 – 39.9N·m

12.8 – 13.2

 φ

 12.7

(1/2”)

49.5 – 60.3N·m

16.2 – 16.6

 φ

 15.9

(5/8”)

61.8 – 75.4N·m

19.3 – 19.7

A

45

0

±2

0

R0.4-0.8

90

0

±2

0

Indoor units to be 

connected

Gas piping diameter

Liquid piping 

diameter

FXMQ200M(A)VE, 

MAV7

φ

19.1

Use attached piping.

φ

9.5

FXMQ250M(A)VE, 

MAV7

φ

22.2

Use attached piping.

φ

9.5

     

  

 

 

Small

sealing pad
(accessory)

Insulation for

fitting (accessory)

Gas pipe

Liquid pipe

(for gas line)

Clamp (× 4)

(accessory)

01_EN_3P258319-6F.fm  Page 5  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...

Reviews: