CAUTION

• Be sure to attach the sealing material or putty (field supplied) 

to hole of wiring to prevent the infiltration of water as well as 
any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the control box.

• When clamping the wires, be sure no tension is applied to the 

wire connections by using the included clamping material to 
make appropriate clamps. Also, when wiring, make sure the 
lid on the control box fits snugly by arranging the wires neatly 
and attaching the control box lid firmly. When attaching the 
control box lid, make sure no wires get caught in the edges. 
Pass wiring through the wiring through holes to prevent dam-
age to them.

• Make sure the remote controller wiring, the wiring between 

the units, and other electrical wiring do not pass through the 

same locations outside of the unit, separating them by at 
least 50mm, otherwise electrical noise (external static) could 
cause mistaken operation or breakage. 

[ PRECAUTIONS ] 

1.

Use round crimp-style terminals for connecting wires to the 
power supply terminal block. 

If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same 

power supply terminal.
(Looseness in the connection may cause overheating.)

• Use the specified electric wire. Connect the wire securely 

to the terminal. Lock the wire down without applying 
excessive force to the terminal. (Tightening torque: 
131N·cm ±10 %)

2. Tightening torque for the terminal screws.

• Use the correct screwdriver for tightening the terminal 

screws. If the blade of screwdriver is too small, the head 
of the screw might be damaged, and the screw will not be 
properly tightened.

• If the terminal screws are tightened too hard, screws 

might be damaged.

• Refer to the table below for the tightening torque of the 

terminal screws.

3. Do not connect wires of different gauge to the same ground-

ing terminal. Looseness in the connection may deteriorate 
protection.

4. Outside of the unit, keep transmission wiring at least 50 mm 

away from power supply wiring. The equipment may mal-
function if subjected to electrical (external) noise. 

5. For remote controller wiring, refer to the “INSTALLATION 

MANUAL OF REMOTE CONTROLLER” attached to the 
remote controller. 

6.

Never connect power supply wiring to the terminal 
block for remote controller wiring. A mistake of the sort 
could damage the entire system.

7. Use only specified wire and tightly connect wires to termi-

nals. Be careful wires do not place external stress on termi-
nals. Keep wiring in neat order and so as not to obstruct 
other equipment such as popping open the control box lid. 
Make sure the lid closes tight. Incomplete connections 
could result in overheating, and in worse case, electric 
shock or fire.

 FXMQ200 · 250M(A)VE, MAV7 

Control 
box lid

Transmission 
wiring (*)

Ground wiring

Power supply 
wiring (*)

(Field wiring)

Remote controller 
wiring (*)

(Field wiring)

(Field wiring)

Wiring (*)

(Remote controller 
 and transmission)

Wire locking 
bracket

Clamp
(accessory)

FXMQ40 · 50 · 63 · 80 · 100 · 125M(A)VE

T2
T1
F2
F1
P2
P1

Power supply

wiring,

ground wiring

Clamp

Power

supply

terminal

block

Terminal

block for

remote

controller

(accessory)

Remote

controller

wiring

X2M

X1M

Field

supply

wire

Transmission

wiring

FXMQ200 · 250M(A)VE, MAV7

Clamp (accessory)

Power supply

terminal block

Terminal block

for remote

controller

Remote

controller wiring

X2M

X1M

Transmission wiring

Power supply wiring

and ground wiring

 

   

  

Terminal

Size

Tightening torque

Terminal block for remote controller (6P)

40 – 125 (2P)

200·250  (3P)

40 – 125

200 · 250

M3.5

0.79 – 0.97 N·m

Power supply terminal block

Ground terminal

M4

M4

M4

M5

1.18 – 1.44 N·m

1.18 – 1.44 N·m

1.44 – 1.94 N·m

3.02 – 4.08 N·m

01_EN_3P258319-6F.fm  Page 8  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...

Reviews: