(4) Add remote control 2 (slave) to the terminal block for 

remote controller (P

1

, P

2

) in the control box. 

(There is no polarity.)  (Refer to Fig. 3 and 8-3.)

9-4

EXTERNAL REMOTE CONTROL (FORCED 
OFF AND ON/OFF OPERATION) 

(1) Wire specifications and how to perform wiring 

• Connect the input from outside to terminals T1 and T2 of 

the terminal block for remote controller.

(2) Actuation 

• The following table explains FORCED OFF and ON/OFF 

OPERATIONS in response to Input A. 

(3) How to select FORCED OFF and ON/OFF OPERATION 

• Turn the power on and then use the remote controller to 

select operation. 

9-5 CENTRALIZED CONTROL 

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional controller 
for centralized control.

10. FIELD SETTING

Make sure the terminal box lids are closed on the indoor 
and outdoor units.
Field setting must be made from the remote controller in 
accordance with the installation condition.

• Setting can be made by changing the “Mode No.”, “FIRST 

CODE NO.”, and “SECOND CODE NO.”.

• For setting and operation, refer to the “FIELD SETTING” in 

the installation manual of the remote controller.

• Set the remote controller to the field set mode. For 

details, refer to the “HOW TO SET IN THE FIELD”, in the 
remote controller manual. 

• When in the field set mode, select mode No. 12, then set 

the first code (switch) No. to “1”. Then set second code 

(position) No. to “01” for FORCED OFF and “02” for ON/
OFF OPERATION. (FORCED OFF at factory set)

11. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when 

an malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An expla-
nation of malfunction codes and the corresponding trouble is 
provided in “CAUTION FOR SERVICING” of the outdoor 
unit.
If any of the items in Table 4 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 4

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum appli-
cable load of 15 V DC, 1 mA.

FORCED OFF

ON/OFF OPERATION

Input ON stops operation (impossible by 
remote controllers.)

Input OFF 

→ 

ON turns 

ON unit.

Input OFF enables control by remote con-
troller.

Input ON 

→ 

OFF turns 

OFF unit.

  

  

SETTING

 

 

   

 

 

Remote control display

Content

“Concentrated Management” 

is lit up

• There is a short circuit at the 

FORCED OFF terminals (T1, T2)

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is 

off.

• The outdoor unit has not been 

wired for power supply.

• Incorrect wiring for the transmis-

sion wiring and / or FORCED 

OFF wiring.

No display

• The power on the indoor unit is 

off.

• The indoor unit has not been 

wired for power supply.

• Incorrect wiring for the remote 

controller wiring, the transmission 

wiring and / or the FORCED OFF 

wiring.

01_EN_3P258319-6F.fm  Page 10  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...