English

7

CAUTION

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

8. ELECTRIC WIRING WORK 

8-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.
• For electric wiring work, refer to also “Wiring diagram label” 

attached to the control box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B..., and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. 
If wiring and piping between the outdoor unit and an indoor 
unit are mismatched, the system may cause a malfunction.

• A main switch or other means for disconnection, having a 

contact separation in all poles, must be incorporated in the 
fixed wiring in accordance with relevant local and national 
legislation.
Note that the operation will restart automatically if the main 
power supply is turned off and then turned back on again.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply wiring connected to the outdoor 
unit, the capacity of the circuit breaker and switch, and wiring 
instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light-

ning rods, or telephone ground wires.

• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is 

used.

• Telephone ground wires or lightning rods : might cause 

abnormally high electric potential in the ground during 
lighting storms.

8-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) 
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

NOTE

1.

Allowable length of transmission wiring between indoor/outdoor units 
and between the indoor unit and the remote controller is as follows. 

(1) Outdoor unit – Indoor unit: 

Max. 1000 m (Total wiring length: 2000 m) 

(2) Indoor unit – Remote controller: 

Max. 500 m

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

(Remove the control box lid and wire as shown in the figure below.)

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

FXMQ40 · 50 · 
63M(A)VE

50

220-

240

Max. 264
Min.  198

1.3

15

0.100

1.0

FXMQ80M(A)VE

1.5

15

0.160

1.2

FXMQ100M(A)VE

2.5

15

0.270

2.0

FXMQ125M(A)VE

3.8

15

0.430

3.0

FXMQ200M(A)VE

8.1

15

0.380×2

6.5

FXMQ250M(A)VE

9.0

15

0.380×2

7.2

FXMQ200MAV7

50

220

Max. 242

Min. 198

8.1

15

0.380×2

6.5

FXMQ250MAV7

9.0

15

0.380×2

7.2

FXMQ40 · 50 · 
63M(A)VE

60

220

Max. 242
Min.  198

1.4

15

0.100

1.1

FXMQ80M(A)VE

1.6

15

0.160

1.3

FXMQ100M(A)VE

3.0

15

0.270

2.4

FXMQ125M(A)VE

4.4

15

0.430

3.5

FXMQ200M(A)VE

9.0

15

0.380×2

7.2

FXMQ250M(A)VE

10.1

15

0.380×2

8.1

Model

Power supply wiring

Remote controller wiring

Transmission wiring

Field fuses 

Wire

Size

Wire

Size

FXMQ40 · 50 · 
63M(A)VE

15A

H05VV-

U3G

Size must  
comply 
with local 
codes.

Sheathed 
wire 
(2 wire)

0.75 - 

1.25 mm

2

FXMQ80M(A)VE

FXMQ100M(A)VE

FXMQ125M(A)VE

FXMQ200M(A)VE, 
MAV7

FXMQ250M(A)VE, 
MAV7

FXMQ40 · 50 · 63 · 80 · 100 · 125M(A)VE

Power supply wiring (*)

Ground wiring

Remote controller 
wiring (*)

(Field wiring)

(Field wiring)

(Field wiring)

Control box lid

Transmission 
wiring (*)

Wiring (*)

(Remote controller and transmission)

Wire locking 
bracket

Clamp

(accessory)

01_EN_3P258319-6F.fm  Page 7  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...