4. PREPARATIONS BEFORE INSTALLA-

TION

(1) Relative positions of indoor unit and suspension bolt. 

(Refer to Fig. 2)

(2) Install a canvass duct to the air discharge outlet and air inlet 

so that vibration from the machine body isn’t transmitted to 
the duct or ceiling.
You should also apply sound absorbing material to the 
inside of the duct, and vibration insulation rubber to the sus-
pension bolts.

(3) Install suspension bolts.

(Use bolts of 10 mm diameter.)
• Install the equipment where supporting structures are 

strong enough to bear the equipment’s weight. Use 
embedded inserts or anchor bolts with new buildings and 
hole-in-anchors with old buildings.

5. INDOOR UNIT INSTALLATION

Installing optional accessories before installing the indoor 

unit is easier.

As for the parts to be used for installation work, be sure to use 

the provided accessories and specified parts designated by our 

company.

(1) Fix the hanger bracket to the suspension bolt. Tighten both 

upper and lower nuts firmly using washers.

(2) Adjust the height of the unit.
(3) Make sure the unit is 

level.
• Level the unit with 

a level when 
installing. If the unit 
is not level, it could 
become the source 
of water leaks.

• When leveling the 

unit, check all four 
corners with a level 
or a vinyl tube con-
taining water. (See 
the figure on the 
right.)

(4) Tighten the nuts on the top.
(5) Insulate the two hanger brackets on the discharge side with 

the sealing pad. (× 2) Insulate the edges so that the surface 
and edges of the hanger brackets cannot be seen. 
(FXMQ200 · 250M(A)VE, MAV7)

CAUTION

Setting the unit at an angle opposite to the drain piping 
might cause leaks.

FXMQ200 · 250M(A)VE, MAV7

FXMQ40 · 50 · 63 · 80 · 100 · 125M(A)VE

740

690

Indoor unit

Suspension bolt (× 4)

Air inlet

Inspection hatch

450

Air outlet

A

B

Fig. 2

Indoor unit

Air outlet

Inspection hatch

600

1296

Air inlet

Approx. 150

mm

1100

1100 or more

1148

1380

(service space)

Suspension

bolt (× 4)

Model

A

670

1060

B

720

1110

FXMQ40M(A)VE

50M(A)VE

63M(A)VE

80M(A)VE

FXMQ100M(A)VE

125M(A)VE

(length: mm)

650

or

more

(service

space)

  

     

 

       

  

 

Part to be procured in the field

Tighten from above and below

(Double nut)

Washer (accessory)

   

A-A cross-section

 

 

 

   

B-B cross-section

01_EN_3P258319-6F.fm  Page 4  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...

Reviews: