background image

6

English

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filler metal (BCuP-2: JIS Z 
3264/B-Cu93P-710/795: ISO 3677) which does not require 
flux.
(Flux has extremely harmful influence on refrigerant piping 
systems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow the 
installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below:

Table 3

7. DRAIN PIPING WORK

〈〈

Rig the drain pipe as shown below and take measures 

against condensation. Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.

〉〉

〈〈

Insulate the drain hose inside the building.

〉〉

(1) Carry out the drain piping.

• Keep piping as short as possible and slope it downwards 

so that air may not remain trapped inside the pipe.

• Keep pipe size equal to or greater than that of the con-

necting pipe (Vinyl pipe of 25 mm nominal diam. and 
32 mm outer diam.).

• Use the attached drain hose and clamp.

Tighten the clamp firmly.

• Insulate the clamp metal with the sealing pad.

There is negative pressure inside the unit relative to atmo-
spheric pressure when the unit is running, so be sure to 
provide drain trap on the drain outlet. (See the figure)

In order to prevent foreign matter from building up 
inside the piping, you should avoid curves as much 
as possible, and arrange so the trap can be cleaned.

NOTE

• If converging multiple drain pipes, install according to the pro-

cedure shown below. (Install a drain trap for each indoor unit.)

• A drain trap need not be installed.
• The diameter of the piping is the same as that of the con-

necting pipe (PS1B), and should be kept equal to or 
greater than that of the connecting pipe.

(2) After piping work is finished, check drainage flows 

smoothly.

• Add approximately 1 liter of water slowly from the air inlet 

and check drainage flow.

• Open the water supply port, add approximately 1 liter of 

water slowly into the drain pan and check drainage flow.

Pipe size

Further tightening 

angle

Recommended arm length of 

tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressurereducing valve

Hands 
valve

Nitrogen

FXMQ40-125M(A)VE

FXMQ200 · 250M(A)VE, MAV7

FXMQ40-125M(A)VE

FXMQ200 · 250M(A)VE, MAV7

50mm or 

more

50mm or 

more

Bottom of unit

Attached drain hose

Metal clamp

Drain hose

Tape

4mm or less

Drain hose

Large sealing pad

(accessory)

Metal clamp

(accessory)

100mm 

or more

01_EN_3P258319-6F.fm  Page 6  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...

Reviews: