VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1
2. BEFORE INSTALLATION................................................ 2
3. SELECTING INSTALLATION SITE ................................. 3
4. PREPARATIONS BEFORE INSTALLATION ................... 4
5. INDOOR UNIT INSTALLATION....................................... 4
6. REFRIGERANT PIPING WORK ..................................... 5
7. DRAIN PIPING WORK .................................................... 6
8. ELECTRIC WIRING WORK ............................................ 7
9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER ....................................... 7

10. FIELD SETTING............................................................ 10

11. TEST OPERATION ....................................................... 10

The original instructions are written in English. All other lan-
guages are translations of the original instructions.

1. SAFETY PRECAUTIONS

Be sure to follow this “SAFETY PRECAUTIONS”. 
This product comes under the term “appliances not accessible 
to the general public”.
This is a class A product. In a domestic environment this prod-
uct may cause radio interference in which case the user may be 
required to take adequate measures.

This manual classifies the precautions into WARNINGS and 
CAUTIONS.
Be sure to follow all the precautions below: They are all impor-
tant for ensuring safety.

WARNING

  ............ Indicates a potentially hazardous situ-

ation which, if not avoided, could 
result in death or serious injury.

CAUTION

 .............. Indicates a potentially hazardous situa-

tion which, if not avoided, may result in 
minor or moderate injury.
It may also be used to alert against 
unsafe practices.

• After the installation is completed, test the air conditioner and 

check if the air conditioner operates properly. Give the user 
adequate instructions concerning the use and cleaning of the 
indoor unit according to the Operation Manual. Ask the user 
to keep this manual and the Operation Manual together in a 
handy place for future reference.

WARNING

• Ask your local dealer or qualified personnel to carry out 

installation work.
Improper installation may result in water leakage, electric 
shocks or a fire.

• Perform installation work in accordance with this installation 

manual.
Improper installation may result in water leakage, electric 
shocks or a fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage.
When the air conditioner is installed in a small room, it is nec-
essary to take proper measures so that the amount of any 
leaked refrigerant does not exceed the concentration limit in 
the event of a leakage.

Otherwise, this may lead to an accident due to oxygen defi-
ciency.

• Be sure to use only the specified parts and accessories for 

installation work.
Failure to use the specified parts may result in the air condi-
tioner falling down, water leakage, electric shocks, a fire, etc.

• Install the air conditioner on a foundation that can withstand 

its mass.
Insufficient strength may result in the air conditioner falling 
down and causing injury.
In addition, it may lead to vibration of indoor units and cause 
unpleasant chattering noise.

• Carry out the specified installation work in consideration of 

strong winds, typhoons, or earthquakes. Improper installa-
tion may result in an accident such as air conditioner falling.

• Make certain that all electrical work is carried out by qualified 

personnel according to the applicable legislation (note 1) and 
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wir-
ing that has sufficient length and never connect additional 
wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shocks or a fire.
(note 1) applicable legislation means “All international, 

national and local directives, laws, regulations 
and/or codes which are relevant and applicable for 
a certain product or domain”.

• Earth the air conditioner.

Do not connect the earth wiring to gas or water piping, light-
ning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage circuit breaker.

Failure to do so may cause electric shocks and a fire.

• Disconnect the power supply before touching the electric 

components.
If you touch the live part, you may get an electric shocks.

• Make sure that all wiring is secure, using the specified wiring 

and ensuring that external forces do not act on the terminal 
connections or wiring.
Incomplete connection or fixing may cause an overheat or a 
fire.

• When wiring between the indoor and outdoor units, and wir-

ing the power supply, form the wiring orderly so that the con-
trol box lid can be securely fastened.
If the control box lid is not in place, overheat of the terminals, 
electric shocks or a fire may be caused.

• If refrigerant gas leaks during installation work, ventilate the 

area immediately.
Toxic gas may be produced if refrigerant gas comes into con-
tact with a fire.

• After completing the installation work, check to make sure 

that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the 
room and comes into contact with a source of a fire, such as 
a fan heater, stove or cooker.

• Never directly touch any accidental leaking refrigerant. This 

could result in severe wounds caused by frostbite.

01_EN_3P258319-6F.fm  Page 1  Tuesday, June 3, 2014  11:36 AM

Summary of Contents for FXMQ100MAVE

Page 1: ...DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLAT...

Page 2: ...VE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ1...

Page 3: ...ire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibra...

Page 4: ...ches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an o...

Page 5: ...lowable limit Refer to the installation manual of the outdoor unit CAUTION Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radio...

Page 6: ...2 Adjust the height of the unit 3 Make sure the unit is level Level the unit with a level when installing If the unit is not level it could become the source of water leaks When leveling the unit che...

Page 7: ...flare section both inside and outside with ester oil or ether oil rotate three or four times first then screw in Refer to the Table 2 for tightening torque Ventilate if refrigerant gas leaks while per...

Page 8: ...Insulate the drain hose inside the building 1 Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal...

Page 9: ...sed Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps...

Page 10: ...table below for the tightening torque of the terminal screws 3 Do not connect wires of different gauge to the same ground ing terminal Looseness in the connection may deteriorate protection 4 Outside...

Page 11: ...F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 L N Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor unit C Most downstream Indoor unit Power suppl...

Page 12: ...et second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the r...

Page 13: ...1406 FS 3P258319 6F EM02A083G 00_CV_3P258319 6F fm Page 2 Tuesday June 3 2014 11 50 AM...