background image

8

English

Table 2

(2) On completion of installation work, 

check that there is no 

gas leakage

.

(3) Refer to the following illustration and be sure to perform 

heat insulation work on the piping joints after gas leakage 
checks. 

(Refer to Fig. 6)

• Use the insulation for fitting (4) and (5) provided to the 

liquid piping and gas piping, respectively, and conduct 
heat insulation work.
(Tighten both edges of the insulation for fitting (4) and (5) 
for each joint with the clamp (8).)

• Make sure that the joint of the insulation for fitting (4) and 

(5) for the joint on the liquid piping and gas piping side 
faces upward.

• Wrap the middle sealing material (7) around the insula-

tion for fitting (4) and (5) for the joint (flare nut part).

CAUTION

• Be sure to perform the heat insulation of the local piping 

up to the piping joint.

If the piping is exposed, dew condensation may result. Fur-
thermore, a burn may be caused if a human body comes in 
contact with the piping.

• Perform nitrogen substitution or charge the refrigerant 

piping with nitrogen (see NOTE 1) in the case of refriger-
ant piping brazing (see NOTE 2). Then perform the flare 
connection of the indoor unit. 

(Refer to Fig. 7)

CAUTION

• Do not use any antioxidant at the time of piping brazing.

The piping may be clogged with a residual antioxidant and 
parts may malfunction.

NOTE

1. At the time of brazing, set the pressure of nitrogen to 

approximately 2.9 PSI (0.02 MPa) (close to the pressure 
of a breeze coming in contact with the cheek) with a pres-
sure reducing valve.

2. Do not use flux at the time of brazing and connecting the 

refrigerant piping. Use a copper phosphorus brazing alloy 
(BCuP-2/BCu 93P-710/795), which does not require flux, 
for brazing.
(Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if 
it contains fluorine, the flux will deteriorate refrigerant oil.)

• As for the branching of the refrigerant piping or refrigerant, 

refer to the installation manual provided with the outdoor unit.

7.

DRAIN PIPING WORK

(1) Conduct drain piping work.

Check that the piping 
ensures proper draining.

• Make sure that the diam-

eter of the piping exclud-
ing the rising part is the 
same as or larger than 
the diameter of the con-
necting pipe (vinyl chloride pipe with an outer diameter 
of 1-1/4 in. (32 mm) and a nominal inner diameter of 31/
32 in. (25 mm)).

• Make sure that the piping is short enough 

with a down-

ward slope of at least 1/100

 and that there is no air 

bank formed. No drain trap is required.

Piping size

[in. (mm)]

Tightening

angle

Recommended arm length of

tool used



1/4 (6.4)

60° – 90°

Approx. 6 in. (150 mm)



3/8 (9.5)

60° – 90°

Approx. 8 in. (200 mm)



1/2 (12.7)

30° – 60°

Approx. 10 in. (250 mm)



5/8 (15.9)

30° – 60°

Approx. 12 in. (300 mm)

Heat insulation procedure for gas piping

Insulation material 
for piping 
(on unit side)

Insulation material 
for piping (field supply)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Gas pipe

Liquid pipe

Flare nut joint

Attached to 
the surface.

Insulation for fitting (5) (accessory)

Middle sealing pad (7) 
(accessory)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Insulation material 
for piping (field supply)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Fig. 6

Heat insulation procedure for liquid piping

Insulation material 
for piping 
(on unit side)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Main unit

Flare nut joint

Attached to 
the surface.

Insulation for fitting (4) (accessory)

Middle sealing pad (7) 
(accessory)

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressure reducing valve

Hands 
valve

Nitrogen

Fig. 7

Refrigerant 
piping

Drain socket 

Socket for 
maintenance 
(with rubber cap)

01_EN_3PN14093-18K.fm  Page 8  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: