background image

14

English

No. 3 system: When including BS unit

[ PRECAUTIONS ] 

1. Do not ground the equipment on gas pipes, water pipes or 

lightning rods, or crossground with telephones. Improper 
grounding could result in electric shock.

2. The remote controller wiring (P1 and P2) and transmission 

wiring (F1 and F2) have no polarity.

NOTE

This equipment can be installed with a Ground-Fault Circuit 
Interrupter (GFCI). Although this is a recognized measure for 

additional protection, with the grounding

 system in North Amer-

ica, a dedicated GFCI is not necessary.

10-3 COMPUTERISED CONTROL (FORCED OFF 

AND ON/OFF OPERATION) 

(1) Wire specifications and how to perform wiring 

• Connect the external input to terminals T1 and T2 of the 

terminal block for remote controller.

(2) Actuation 

• The following table explains FORCED OFF and ON/OFF 

OPERATIONS in resp

onse to Input A. 

(3) How to select FORCED OFF and ON/OFF OPERATION 

• Turn the power on and then use the remote controller to 

select operation. 

10-4 CENTRALIZED CONTROL 

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional control-
lers for centralized control.
(Refer to 

11. FIELD SETTING)

11. FIELD SETTING

CAUTION

When performing field setting or test run without attaching 

the decoration panel, do not touch the drain pump. This 

may cause electric shock.

• Check that the outdoor unit has been wired properly.

1. Make sure the control box cover is closed on the indoor 

and outdoor units.

2. Field settings must be made from the remote controller 

and in accordance with installation conditions.

• Settings can be made by changing the “Mode No.”, 

“FIRST CODE NO.” and “SECOND CODE NO.”.

• The “Field Settings” included with the remote control lists 

the order of the settings and method of operation.
Setting is made in all units in a group. To set for individual 
indoor units or to check the setting, use the mode No. 
(with “2” in upper digit) in parentheses ( ).

With Wireless Remote Controller Used

Set the wireless remote controller address before using the 
wireless remote controller.
For the setting method of the address, refer to the operation 
manual provided with the wireless remote controller.

NOTE

• A MODE NO. is set on a group basis. To make a mode setting 

on a room unit basis or check the setting made, however, set 
the corresponding mode number in the parentheses.

1. Settings for Optional Accessories

• In the case of connecting optional accessories, refer to 

the operation manuals provided with the optional acces-
sories and make necessary settings.

2. External Static Pressure Settings

Make settings in either method (a) or method (b) as 

explained below.
(a)

Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is 
automatically adjusted to the rated quantity.

Wire specification

Sheathed vinyl cord or cable (2-wire)

Gauge

AWG18-16

Length

Max. 328 ft. (100 mm)

External terminal

Contact that can ensure the minimum appli-
cable load of 15 V DC, 1 mA.

FORCED OFF

ON/OFF OPERATION

Input ON stops operation (impossible by 
remote controllers.)

Input OFF 



ON turns 

ON unit.

Input OFF enables control by remote con-

troller.

Input ON 



OFF turns 

OFF unit.

Outdoor unit

BS unit

L

1

L

2

Indoor unit A

Remote controller

(option)

F

F

1

2

F

F

1

2

F

F

1

2

F

F

1

2

IN/D

IN/D

OUT/D

OUT/D

1

P

P

2

1

F

2

L

2

F

L

1

1

2

T T

1

P

2

P

Power supply

single phase

60Hz 208/230V

F2

T1

T2

FORCED
OFF

Input A

FIELD SET MODE

MODE NO.

FIRST CODE NO.

SECOND CODE NO.

01_EN_3PN14093-18K.fm  Page 14  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: