background image

English

15

(1) Check that power supply wiring to the air conditioner 

is completed along with duct installation. If a closing 
damper is installed in the air-conditioning system, 
make sure that the closing damper is opened. Fur-
thermore, check that the air filter as a field supply is 
attached to the air passage on the suction side.

(2) If there are a number of air outlets and inlets, adjust the 

throttles so that the airflow rate of each air outlet and 
inlet will coincide with the designed airflow rate. At that 
time, operate the air conditioner in FAN operation mode. 
To change the airflow rate, press and set the airflow 
adjustment button of the remote controller to HH, H, or L.

(3) Make settings for airflow automatic adjustment. After 

setting the air conditioner to FAN operation mode, 
stop the air conditioner, go to FIELD SET MODE, 
select MODE NO. 21 (11 in the case of group set-
tings), set the setting FIRST CODE NO. to 7, and set 
the setting SECOND CODE NO. to 03. 
Return to normal mode after these settings, and press 
the ON/OFF OPERATION button. Then the operation 
lamp will be lit and the air conditioner will go into fan 
operation for airflow automatic adjustment. Do not 
adjust the throttles of the air outlets or inlets during 
automatic adjustment of the air conditioner. After the 
air conditioner runs approximately one to eight min-
utes, the air conditioner will finish airflow adjustment 
automatically, the operation lamp will be turned OFF, 
and the air conditioner will come to a stop.

Table 3

(4) After the air conditioner stops operating, check with 

MODE NO. 21 on an indoor unit basis that 02 is set 
for the SECOND CODE NO. in Table 3. If the air con-
ditioner does not stop operating automatically or the 
SECOND CODE NO. is not 02, repeat steps from (3). 
If the outdoor unit is not turned ON, U4 or UH as 
explained in Table 9 will be displayed. This display is 
not problematic, because this function is set for the 
indoor unit. Continue setting the function. After set-
ting this function, be sure to turn ON the outdoor unit 
before the test operation of the outdoor unit. If any 
other error is displayed, refer to Table 9 and the oper-
ation manual provided with the outdoor unit and 
check the defective point.

CAUTION

• If there is any change after airflow adjustment in the ventila-

tion paths (e.g., the duct and air outlet), be sure to make air-
flow auto adjustment again.

• Consult your Daikin representative if there is any change in 

the ventilation paths (e.g., the duct and air outlet) after the test 
operation of the outdoor unit is finished or the air conditioner 
is moved to another place.

(b) Select External Static Pressure with Remote Controller

Check that 01 (OFF) is set for the SECOND CODE NO. 
in MODE NO. 21 for airflow adjustment on an indoor unit 
basis in Table 3. The SECOND CODE NO. is set to 01 
(OFF) at factory set. Change the SECOND CODE NO. 
as shown in Table 4 according to the external static pres-
sure of the duct to be connected.
(1) The SECOND CODE NO. is set to 07 (an external 

static pressure of 0.40 inWG (100 Pa)) at factory set. 
(FXMQ15 · 18 · 24 · 30 · 36 · 48 · 54PBVJU)
The SECOND CODE NO. is set to 02 (an external 
static pressure of 0.20 inWG (50 Pa)) at factory set. 
(FXMQ07 · 09  · 12PBVJU)
*1 The FXMQ15 · 18 · 24 · 30 · 36 · 48PBVJU cannot 

be set to 0.12 inWG (30 Pa).

*2 The FXMQ07 · 09 · 12PBVJU cannot be set to 

0.44-0.80 inWG (110-200 Pa).

*3 The FXMQ54PBVJU cannot be set to 0.12 inWG 

(30 Pa) and 0.60-0.80 inWG (150-200 Pa).

Table 4

CAUTION

Keep in mind that a shortage of airflow quantity or water leakage 
will result because the air conditioner will be operated outside 
the rated range of airflow quantity if the external static pressure 
is wrongly set.

3. Filter Sign Settings

• The remote controller is provided with an LCD that tells 

the time of air filter cleaning.

• If the air conditioner is used in places with excessive dust, 

change the SECOND CODE NO. as shown in Table 5. 
The SECOND CODE NO. is set to 01 (standard) at fac-
tory set.

MODE NO.

FIRST CODE NO.

Setting contents

11 (

21

)

7

Airflow 

adjustment

SECOND CODE NO.

01

02

03

OFF

Completion of 

airflow adjustment

Start of airflow 

adjustment

External Static Pressure

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE NO.

0.12 inWG (30 Pa) (*1)

13 (23)

06

01

0.20 inWG (50 Pa)

02

0.24 inWG (60 Pa)

03

0.28 inWG (70 Pa)

04

0.32 inWG (80 Pa)

05

0.36 inWG (90 Pa)

06

0.40 inWG (100 Pa)

07

0.44 inWG (110 Pa) (*2)

08

0.48 inWG (120 Pa) (*2)

09

0.52 inWG (130 Pa) (*2)

10

0.56 inWG (140 Pa) (*2)

11

0.60 inWG (150 Pa) (*2)

12

0.64 inWG (160 Pa) (*2)

13

0.72 inWG (180 Pa) (*2)

14

0.80 inWG (200 Pa) (*2)

15

01_EN_3PN14093-18K.fm  Page 15  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: