background image

12

English

(2) Lay the wires in the control box through the wire inlet on the 

side of the control box.

CAUTION

• Do not lay the remote controller wiring or transmission wiring 

along with the power supply wiring or other electric wiring in 

the same route. Separate the remote controller wiring and 
transmission wiring at least 2 in. (50 mm) from the power sup-
ply wiring or other electric wiring, or otherwise malfunctions or 
failures may be caused by external electric noise that may 
interfere with the remote controller wiring and transmission 

wiring.

• For the installation and wiring of the remote controller, refer to 

the remote controller installation manual provided with the 
remote controller.

• For power supply wiring, refer to the wiring diagram as well.
• Be sure to connect the remote controller wiring and transmis-

sion wiring correctly to the right terminal block.

(3) Follow the instructions below, and lay the wires in the con-

trol box.

Routing power supply wiring and transmission wiring
Let the power supply wiring with a conduit pass through one of 

the holes on the side cover, and let the transmission wiring with 

a conduit pass through another hole.

• For protection from uninsulated live parts, thread the power 

supply wiring or the transmission wiring through the included 
insulation tube and secure it with the included clamp.

When use the insulation tube

• Cut off the insulation tube as need length.

WARNING

Trim and lay the wiring neatly and attach the control box 

cover securely.

An electric shock or fire may result if the control box cover 
catches any wiring or the wires push up the cover.

Low-voltage wiring inlet

Transmission wiring
(Low voltage)
Remote controller wiring
(Low voltage)

Lock nut
(Field supply)

Elbow
(Field supply)

Conduit
(Field supply) 

High-voltage wiring inlet

Power supply wiring (High voltage)
Ground wiring (High voltage)

L

1

L

2

1

P

2

P

1

F

2

F

1

T

2

T

Fix the wires with 
clamp (8) to the 
wire fixing bracket 
provided to the 
control box.

Insert the cord into 
the wire clips 
provided with the 
control box.

PROHIBITED

Never connect the power 
supply wiring.

Connection method of remote 
controller terminals (X2M) 

• If stranded wires are used, do 

  not solder the front end of the 
 wires.

Twist and fix the upper part so 
that the wires will not drop out.

Fix the cord with the 
clamp (8) to the wire 
fixing bracket provided 
to the control box.

Remote controller 
wiring (No polarity)

Power supply wiring 
(High voltage)
Ground wiring 
(High voltage)

Transmission wiring 
(No polarity)

Transmission 
wiring (Low voltage)
Remote controller 
wiring (Low voltage)

Ground

Connection method of 
power supply terminals 
(X1M)

Insulation tube
(accessory (12))

Conduit
(field supply)

Insulation tube
(accessory (12))

Clamp
(accessory (8))

Power supply wiring 

or

Transmission wiring

(3 in. (75 mm))

Cut off

01_EN_3PN14093-18K.fm  Page 12  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: