background image

English

7

CAUTION

• Use the level and check that the unit is installed horizontally.

(4 directions)

• In the case of using a vinyl tube (filled with water) in place of 

the level, align the bottom of the unit to the water surface at 
both edges of the vinyl tube to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set 
high, in particular, the float switch will not operate normally 
and water leakage may result.

6.

REFRIGERANT PIPING WORK

As for the refrigerant piping of the outdoor unit, refer to the 

installation manual provided to the outdoor unit.



Perform heat insulation work on both gas piping and liquid 

piping, or otherwise water leakage may result.



Use the insulation material that withstands a temperature 

of 248°F (120°C).



Reinforce the insulation material for the refrigerant piping if 

the ambient temperature is high, or otherwise dew conden-
sation may result on the surface of the insulation material.



Make sure that the refrigerant is R410A before refrigerant 

piping work. If the refrigerant is different, the air condi-
tioner will not operate normally.



CAUTION

This product uses new refrigerant (R410A) only. Be sure to 
keep the following items and conduct the installation work.

• Use a dedicated pipe cutter and flare tool for R410A.
• When connecting the flare, apply ether oil or ester oil 

only to inner side of the flare.

• Be sure to use the flare nut provided with the unit. (Do 

not use a different flare nut (such as a type-1 flare nut), 
or otherwise refrigerant leakage may result.)

• Perform the curing of the piping with pinching or taping 

of the piping in order to prevent the intrusion of dirt, dust, 
and moisture into the piping.

CAUTION

• Be sure to use the specified type of refrigerant for the 

refrigeration cycle and do not contaminate the refrigerant 
with air.

• Ventilate the room in case of refrigerant leakage during 

installation work.

(1) Connect the piping.

• The outdoor unit is filled with refrigerant.
• When connecting or disconnecting piping to or from the 

unit, 

be sure to use a spanner and a torque wrench. 

(Refer to Fig. 4)

• Refer to Table 1 for the processing dimensions of the 

flare.

• Use the flare nut provided with the unit.

Apply ether oil or ester oil only to inner side of the 
flare

 and screw in the flare nut three to four turns first by 

hand at the time of connecting the flare nut. 

(Refer to Fig. 5)

• Refer to Table 1 for the corresponding tightening torque.

Table 1

CAUTION

• Do not excessively tighten the flare nut.

Doing so will break the flare nut and refrigerant leakage may 
result.

• Make sure that all parts around the flare are free of oil.

The drain pan and the resin part may be deteriorated in the 
presence of oil.

• If no torque wrenches are available, refer to Table 2 as a 

standard.
When the flare nut is tightened with the spanner, the 
tightening torque should increase suddenly. Tighten the 
flare nut further for the corresponding angle shown in 
Table 2.

Piping 

size

[in. (mm)]

Tightening 

torque

[lbf·ft. (N·m)]

Dimension for

processing 

flare

A [in. (mm)]

Flare shape



 1/4

(6.4)

10.4 – 12.7

(15.7±1.5)

0.342 – 0.358

(8.9±0.2)



 3/8

(9.5)

24.1 – 29.4

(36.3±3.6)

0.504 – 0.520

(13.0±0.2)



 1/2

(12.7)

36.5 – 44.5

(54.9±5.4)

0.638 – 0.654

(16.4±0.2)



 5/8

(15.9)

45.6 – 55.6

(68.6±6.8)

0.760 – 0.776

(19.5±0.2)

Torque wrench

Spanner

Piping union

Flare nut

Fig. 4

Fig. 5

Apply ester oil or ether oil 
only to inner side of flare.

A

45

0

±2

0

R0.016-0.031

90

0

± 2

0

 

01_EN_3PN14093-18K.fm  Page 7  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: