English
11
CAUTION
Connect the flange and unit with the flange connection screw (3)
regardless of whether the duct is connected to the air inlet side.
9.
ELECTRIC WIRING WORK
9-1
GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to WIRING DIAGRAM attached
to the control box cover.
• For remote controller wiring details, refer to the installation
manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal board
wiring to the outdoor unit and BS unit are properly matched.
If wiring and piping between the outdoor unit and an indoor
unit are mismatched, the system may cause a malfunction.
• A ground fault circuit interrupter capable of shutting down
power supply to the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the ground fault circuit interrupter and
switch, and wiring instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wiring to gas and water pipes,
lightning rods, or telephone ground wires.
• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is
used.
• Telephone ground wires or lightning rods : might cause
abnormally high electric potential in the ground during
lighting storms.
9-2
ELECTRICAL CHARACTERISTICS
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
kW: Fan Motor Rated Output (kW)
FLA: Full Load Ampacity (A)
9-3
SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
Allowable length of transmission wirings and remote controller
wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft (1,000 m) (Total wiring length: 6560 ft
(2,000 m))
(2) Indoor unit – Remote controller:
Max. 1640 ft (500 m)
NOTE
1. Shows only in case of protected pipes. Use H07RN-F in
case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1/16
in. (1 mm) or more)
10. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
10-1 CONNECTING POWER SUPPLY, GROUND,
REMOTE CONTROLLER, AND TRANSMISSION
WIRING
(Remove the control box cover as shown below and connect
each wire.)
(1) Remove the control box cover.
Model
Power supply
Fan motor
Hz
Volts Voltage range MCA
MOP
kW
FLA
FXMQ07PBVJU
60
208V
/230V
Max. 253V
Min. 187V
0.6
15
0.090
0.5
FXMQ09PBVJU
0.6
15
0.090
0.5
FXMQ12PBVJU
1.4
15
0.140
1.1
FXMQ15PBVJU
1.5
15
0.350
1.2
FXMQ18PBVJU
1.6
15
0.350
1.3
FXMQ24PBVJU
1.8
15
0.350
1.4
FXMQ30PBVJU
2.3
15
0.350
2.2
FXMQ36PBVJU
2.9
15
0.350
2.3
FXMQ48PBVJU
3.4
15
0.350
2.7
FXMQ54PBVJU
3.4
15
0.350
2.7
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Field fuses
Size
Wire
Size
FXMQ07PBVJU
15A
Wiring size
and length
must com-
ply with
local
codes.
2-conductor,
stranded
non-shielded
copper cable
PVC/vinyl
jacket
(NOTE 2)
AWG18-16
FXMQ09PBVJU
FXMQ12PBVJU
FXMQ15PBVJU
FXMQ18PBVJU
FXMQ24PBVJU
FXMQ30PBVJU
FXMQ36PBVJU
FXMQ48PBVJU
FXMQ54PBVJU
Screw
(3 portions)
01_EN_3PN14093-18K.fm Page 11 Monday, January 5, 2015 2:52 PM