background image

6

English

(2) Mount the canvas ducts to the air outlet and inlet so that the 

vibration of the air conditioner will not be transmitted to the 
duct or ceiling. Apply a sound-absorbing material (insula-
tion material) to the inner wall of the duct and vibration insu-
lation rubber to the hanging bolts (refer to 

8. DUCT WORK

).

(3) Open installation holes (if the ceiling already exists).

• Open the installation holes on the ceiling. Lay the refrig-

erant piping, drain piping, power line, transmission wir-
ing, and remote controller wiring for the piping and wiring 
connection port of the unit.
In the case of the installation of a wireless remote con-
troller, refer to the installation manual provided with the 
wireless remote controller.
Refer to 

6. REFRIGERANT PIPING WORK

7. DRAIN 

PIPING WORK

, and 

10. WIRING EXAMPLE AND HOW 

TO SET THE REMOTE CONTROLLER

.

• The ceiling framework may need reinforcement in order 

to keep the ceiling horizontal and prevent the vibration of 
the ceiling after the installation holes are opened. For 
details, consult your construction or interior contractor.

(4) Install the hanging bolts. Make sure that the hanging bolts 

are M10 in size.

• Use hole-in anchors if the hanging bolts already exist; 

otherwise use embedded inserts and embedded founda-
tion bolts so that they can withstand the weight of the unit. 
Adjust the distance from the ceiling surface in advance.

5.

INDOOR UNIT INSTALLATION

It may be easier to install accessories (sold separately) 

before installing the indoor unit. Refer to the installation 
manuals provided to the accessories as well.



Be sure to use the accessories and specified parts for 
installation work.

(1) Temporally install the indoor unit.

• Connect the hanging brackets to the hanging bolts. Be 

sure to use and tighten the nut and washer (11) for each 
hanging bracket from both upper and lower sides of the 
hanging bracket. 

(Refer to Fig. 3)

 At that time, the fall of 

the washer (11) for the hanging bracket can be pre-
vented if the washer fixing plate (9) is used.

CAUTION

• During the installation work, perform the curing of the air 

outlet and protect the resin drain pan of the indoor unit 
from the intrusion of foreign substances, such as weld-
ing spatters.

Otherwise, water leakage may occur as a result of damage, 
such as hole damage, to the resin drain pan.

(2) Make adjustments so that the unit will be in the right posi-

tion.

(3) Check the level of the unit.
(4) Remove the washer fixing plates for the falling prevention of 

the washers for the hanging brackets, tighten the nuts on 
the upper side, and securely fix the unit.

Note)   All the above parts are field supplied. 

Installation example

Ceiling slab

Anchor

Long nut or turn-buckle

Hanging bolt

Indoor unit

Washer (11) (accessory)

Part to be procured in the field

Washer fixing plate (9) 
(accessory)

Insert

Tighten from above and below 
(Double nut)

[Fixing hanging brackets]

[Fixing method of washers]

Fig. 3

Nut on the upper side

Hanging bracket

Bottom of product

Level

Vinyl tube

01_EN_3PN14093-18K.fm  Page 6  Monday, January 5, 2015  2:52 PM

Summary of Contents for FXMQ07PBVJU

Page 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Page 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Page 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Page 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Page 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Page 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Page 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Page 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Page 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Page 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Page 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Page 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Page 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Page 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Page 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Page 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Page 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Page 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Reviews: