FXFSQ-AVM EDFMT391769A
39
3P468397-1D
6
CAUTION
Reduce the distance between the unit and ceiling to 35 mm
or below in order to maintain an overlapping panel margin of
20
mm for the opening on the ceiling.
If the distance exceeds 35
mm, attach a ceiling material to
the part marked or replace the ceiling.
(Refer to Fig. 6)
Frame
≥
20
≤
35
≤
35
860 – 910
(Ceiling-panel
overlapping
dimension)
Ceiling
material
(Ceiling opening dimension)
≥
20
Fig. 6
(2) Make the ceiling opening required for installation.
(in case of existing ceiling)
•
Use the installation pattern paper (5) matched to the
ceiling opening dimension.
•
Make the ceiling opening required for installation at the
installation location and carry out refrigerant/drain piping,
power supply wiring, remote controller wiring (not
needed in case of wireless remote controller) and wiring
between the indoor and outdoor units. (Refer to each
•
•
section “
6. REFRIGERANT PIP ING WORK, 7. DRAIN
PIPING WORK and 8. ELECTRIC WIRING WORK ”)
•
After making the opening, sometimes it is necessary to
reinforce the ceiling framework to keep the level of the
ceiling and prevent vibration of the ceiling.
For details, consult with the builder and interior designer.
(3) Install the hanging bolts.
•
Use M8 or M10 bolts for hanging the indoor unit.
Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and
the
indoor unit
to the building so that it may withstand
the mass of the unit.
In addition, adjust clearance (50 - 100 mm) from the
ceiling in advance.
<Installation examples>
50-100 mm
Foundation bolt
Hanging bolt
Ceiling slab
Long nut or turn-buckle
Ceiling surface
Note) The above shown par
ts are all field supply
.
<<It is easy to attach the optional parts (except for
decoration panel) before installing the indoor unit. Refer
to also the installation manual attached to the optional
parts.>>
For installation, use the attached installation parts and
specified
parts.
[Install the indoor unit in the order of steps (1), (2), (3), (4),
and (5) in case of a newly built ceiling, or in the order of steps
(1), (3), (4) and (5) in case of an existing ceiling.]
(1) Install the indoor unit temporarily.
•
Fix the hanger to the hanging bolt.
Make sure to securely the hanger with the nut and
the washer for hanger (3) from the upper and lower side.
(Refer to Fig. 7)
If the washer clamp (7) is used, the upper side washer
for hanger (3) may be protected from falling off.
(Refer to Fig. 8)
[T
o fix hanger]
Hanging bolt
Washer for hanger (3)
(accessory)
Hanger
Tighten the nut
(double nut)
Nut
(Field supply)
Fig. 7
5. INSTALLATION OF INDOOR UNIT
[W
asher clamp (7) fixing method]
Washer clamp (7)
(accessory)
Upper side nut
Insert
Fig. 8
(2)
•
The installation pattern paper (5) is matched to the
ceiling opening dimension.
For the height of ceiling lower surface from the
level,
with the builder of ceiling.
•
The center of the ceiling opening is shown in the
installation pattern paper (5).
The center of the indoor unit is indicated as triangle
marks on the sides and bottom of the unit and those on
the installation pattern paper (5).
•
Put the installation pattern paper (5) to the indoor unit
with four screws (6).
At this time, put the installation pattern paper (5) to the
indoor unit with the triangle marks on the indoor unit and
those on the installation pattern paper (5) aligned.
(unit [mm])
(Dimension inside fr
ame)
840
910
910
(Dimension inside frame)
840
(unit [mm])
Summary of Contents for FXFSQ-AVM
Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Page 2: ......
Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Page 55: ......