background image

FXFSQ-AVM EDFMT391769A

45

3P468397-1D

12

2. Make sure the control box lid is closed before turning

on the power supply.

Throughout the whole process, carry out the work
giving caution to the wiring around the control box
so that the connectors may not come off.

3. Gradually pour 1 liter of water from the air outlet on

the left side of the drain socket into the drain pan
giving caution to avoid splashing water on the electric
components such as drain pump. 

(Refer to Fig. 18)

4. When the power supply is turned on, the drain pump

will operate. Drainage can be checked at the
transparent part of the drain socket.
(The drain pump will automatically stop after 10
minutes.)
After checking the drainage of water, refer to 

Fig. 19

and attach the sealing material (14) to perform the
thermal insulation of the drain socket.

Do not connect the drain piping directly to the
sewage that gives off ammonia odor.
The ammonia in the sewage may go through the
drain piping and corrode the heat exchanger of the
indoor unit.

Do not apply external force to the 

 switch. (It

may result in malfunction)

5. Turn off the power supply after checking drainage,

and remove the power supply wiring.

6. Attach the control box lid as before.

Do not touch the electronic parts other than the
terminal block (X2M).

(3) Sweating may occur and result in water leakage.

Therefore, make sure to insulate the following 2

locations (drain piping and drain sockets that laid

indoors).
After drainage is checked,  put the attached sealing
material (14) referring to 

Fig. 19, and insulate the drain

hose (1) and the metal clamp (2) with the attached sealing
material (Large) (10) referring to 

Fig. 21.

Sealing material (14) 
(accessory)

Sealing material - Large
(10) (accessory)

Be sure to lay the 
sealing material 
(10) on (14).

Do not have 

the clearance.

Fig. 21

Metal

clamp (2)

Drain hose (1)
(accessory)

Sealing material (Large) (10)

(accessory)

(accessory)

4 mm

8. ELECTRIC WIRING WORK

8-1  GENERAL INSTRUCTIONS

Make certain that all electric wiring work is carried out by

qualified

 personnel according to the applicable legislation

and this installation manual, using a separate dedicated
circuit. 

Insufficient

 capacity of the power supply circuit or improper

electrical construction may lead to electric shocks or a 

fir

e.

Make sure to install an earth leakage breaker. 
Failure to do so may cause electrical shocks and a 

fir

e.

Do not turn on the power supply (branch switch, branch
overcurrent circuit breaker) until all the works are 

finished.

Multiple number of indoor units are connected to one
outdoor unit. Name each indoor unit as A-unit, B-unit ….. and
the like. When these indoor units are wired to the outdoor unit
and the BS unit, always wiring the indoor unit to the terminal
indicated with the same symbol on the terminal block. If the
wiring and the piping are connected to the different indoor
units and operated, it will result in malfunction.

Make sure to earth the air conditioner. 
Earthing resistance should be according to applicable
legislation.

Do not connect the earth wiring to gas or water pipings,
lightning conductor or telephone earth wiring.

Gas piping .................Ignition or explosion may occur if 
the gas leaks.

Water piping ..............Hard vinyl tubes are not effective 
earths.

Lightning conductor or telephone earth wiring ..................
 Electric potential may rise abnormally if struck by a light-
ning bolt.

For electric wiring work, refer to also the “WIRING
DIAGRAM” attached to the control box lid.

Carry out wiring between the outdoor units, indoor units and
the remote controllers according to the wiring diagram.

Carry out installation and wiring of the remote controller
according to the “installation manual” attached to the remote
controller.

Do not touch the Printed Circuit Board assembly. It may
cause malfunction.

8-2 ELECTRICAL CHARACTERISTICS

0.3
0.3
0.4
0.4
0.6
1.0
1.4
1.6
1.8
0.3
0.3
0.4
0.4
0.6
1.0
1.4
1.6
1.8

0.2
0.2
0.3
0.3
0.5
0.8
1.1
1.3
1.4
0.2
0.2
0.3
0.3
0.5
0.8
1.1
1.3
1.4

0.053
0.053
0.053
0.053
0.053
0.053
0.106
0.106
0.106
0.053
0.053
0.053
0.053
0.053
0.053
0.106
0.106
0.106

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

Units

Power supply

Fan motor

Model

Hz

Volts Voltage 

range

MCA MFA

kW

FLA

FXFSQ25AVM

50

220-

240

Max. 264

Min. 198

FXFSQ32AVM
FXFSQ40AVM
FXFSQ50AVM
FXFSQ63AVM
FXFSQ80AVM
FXFSQ100AVM
FXFSQ125AVM

FXFQ25AVM

50

220-

240

Max. 264

Min. 198

FXFQ32AVM
FXFQ40AVM
FXFQ50AVM
FXFQ63AVM
FXFQ80AVM
FXFQ100AVM
FXFQ125AVM
FXFQ140AVM

FXFSQ140AVM

Summary of Contents for FXFSQ-AVM

Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...

Page 2: ......

Page 3: ...s 21 6 Electric Characteristics 22 7 Safety Devices Setting 23 8 Capacity Tables 24 8 1 Cooling Capacity for Te Auto 24 8 2 Cooling Capacity for Te 6 C 24 8 3 Cooling Capacity for Te 9 C 25 8 4 Heatin...

Page 4: ...ty index 25 31 25 40 50 62 5 80 100 125 140 FXFSQ 25AVM 32AVM 40AVM 50AVM 63AVM 80AVM 100AVM 125AVM 140AVM FXFSQ for Thailand 25AVS 32AVS 40AVS 50AVS 63AVS 80AVS 100AVS 125AVS 140AVS FXFSQ for Indones...

Page 5: ...es Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950...

Page 6: ...use Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950 9...

Page 7: ...Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950...

Page 8: ...devices Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 95...

Page 9: ...rigerant control Electronic expansion valve Decoration panel option Model BYCQ125EAF Colour Fresh white Dimensions H W D mm 50 950 950 Air filter Resin net with mould resistance Mass kg 5 5 Standard a...

Page 10: ...FXFSQ AVM EDFMT391769A 8 3 Dimensions 3 1 Standard Panel with Sensing Sensor FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112984A Unit mm...

Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...

Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...

Page 13: ...FXFSQ AVM EDFMT391769A 11 3 2 Standard Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112987A Unit mm...

Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...

Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...

Page 16: ...FXFSQ AVM EDFMT391769A 14 3 3 Designer Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112988A Unit mm...

Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...

Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...

Page 19: ...FXFSQ AVM EDFMT391769A 17 3 4 Auto Grille Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112991A Unit mm...

Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...

Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...

Page 22: ...0AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 12 7 6 4 FXFSQ...

Page 23: ...FXFSQ AVM EDFMT391769A 21 5 Wiring Diagrams FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112965A...

Page 24: ...FXFSQ AVM EDFMT391769A 22 6 Electric Characteristics FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM C 3D112911...

Page 25: ...ector Drain pump thermal protector C Model FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal protector Drain pump thermal protector C...

Page 26: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Page 27: ...city kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of...

Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...

Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...

Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...

Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...

Page 32: ...FXFSQ AVM EDFMT391769A 30 10 Centre of Gravity FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 4D052237S Unit mm...

Page 33: ...long life filter Note 9 10 KAFP55H160H Branch duct chamber Note 4 KDJP55C80 Insulation kit for high humidity Note 9 11 KDTP55K80 C 3D112950A Notes 1 When installing designer panel body height ceiling...

Page 34: ...Branch duct chamber Note 4 KDJP55C160 Insulation kit for high humidity Note 9 11 KDTP55K160 C 3D112950A Notes 1 When installing designer panel body height ceiling required dimension is 42 mm higher th...

Page 35: ...tor for electrical appendices Note 1 KRP4AA53 Installation box for adaptor printed circuit board KRP1H98A Note 2 3 Remote sensor for indoor temperature KRCS01 5B External control adaptor for outdoor u...

Page 36: ...cident due to oxygen de ciency Be sure to use only the speci ed parts and accessories for installation work Failure to use the speci ed parts may result in the air conditioner falling down water leaka...

Page 37: ...angers 4 places and do not apply force to other parts particularly refrigerant piping drain piping and resin parts Make sure to check in advance that the refrigerant to be used for installation work i...

Page 38: ...If you wish to use a remote controller that is not listed in Table 2 on page 3 select a suitable remote controller after consulting catalogs and technical materials CARRY OUT THE WORK GIVING CAUTION T...

Page 39: ...e ensured Where the ceiling lower surface is not remarkably inclined Where there is strength to withstand the mass of the indoor unit If the strength is the indoor unit may vibrate and get in contact...

Page 40: ...controller on site Refer to the section 10 FIELD SETTING AND TEST OPERATION 3 Direction of the air discharge Select the number of directions of the optimum air discharge for the shape or the position...

Page 41: ...olt Ceiling slab Long nut or turn buckle Ceiling surface Note The above shown parts are all eld supply It is easy to attach the optional parts except for decoration panel before installing the indoor...

Page 42: ...Check the level of the unit Refer to Fig 9 5 Remove the washer clamp 7 used for preventing the washer for hanger 3 from dropping and tighten the upper side nut Level Vinyl tube Maintaining horizontal...

Page 43: ...Fig 11 Then turn the nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare nut Union joint Fig 10 Coat the ared inner surface only with ether oil or ester oil Fig 11 Table 3...

Page 44: ...the outdoor unit installation manual or technical document for refrigerant piping 5 In case of refrigerant shortage due to forgetting additional refrigerant charge etc it will result in malfunction su...

Page 45: ...Put the metal clamp 2 to the taped hose end and tighten the metal clamp 2 with torque 1 35 0 15 N m 135 15 N cm CAUTION Do not tighten the metal clamp 2 with the torque more than the value The drain h...

Page 46: ...splashing water on the electric components such as drain pump and con rm drainage by operating the indoor unit under cooling mode according to 10 FIELD SETTING AND TEST OPERATION Refer to Fig 18 100 P...

Page 47: ...dedicated circuit Insuf cient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a re Make sure to install an earth leakage breaker Failure to do s...

Page 48: ...Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXF...

Page 49: ...g transmission wiring connecting method Power supply wiring earth wiring Pull the wiring through the wiring penetrating hole high voltage After connecting the power supply wiring to L N on the power s...

Page 50: ...led off After the wirings are clamped cut off the extra part Sheath peeling off allowance P1 P2 F1 F2 T1 T2 10 15 mm Remote controller wiring Transmission wiring Forced off R10 or more Clamp 4 Remote...

Page 51: ...troller 2 Sub to the terminals P1 P2 for remote controller wiring on the terminal block X1M in the control box Wiring penetrating hole Power supply wiring earth wiring or remote controller wiring tran...

Page 52: ...he SECOND CODE No to 01 4 2 For ON OFF OPERATION set the SECOND CODE No to 02 It is set to FORCE OFF when shipped from the factory Ask your customer to keep the manual attached to the remote controlle...

Page 53: ...ng blade 10 1 SETTING CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 5 Table 5 Setting Ceiling height m Mode No FIRST CODE No SECOND CODE No 25 80 type 100...

Page 54: ...ner until the interior work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives used for the interior...

Page 55: ......

Page 56: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Reviews: