FXFSQ-AVM EDFMT391769A
45
3P468397-1D
12
2. Make sure the control box lid is closed before turning
on the power supply.
•
Throughout the whole process, carry out the work
giving caution to the wiring around the control box
so that the connectors may not come off.
3. Gradually pour 1 liter of water from the air outlet on
the left side of the drain socket into the drain pan
giving caution to avoid splashing water on the electric
components such as drain pump.
(Refer to Fig. 18)
4. When the power supply is turned on, the drain pump
will operate. Drainage can be checked at the
transparent part of the drain socket.
(The drain pump will automatically stop after 10
minutes.)
After checking the drainage of water, refer to
Fig. 19
and attach the sealing material (14) to perform the
thermal insulation of the drain socket.
•
Do not connect the drain piping directly to the
sewage that gives off ammonia odor.
The ammonia in the sewage may go through the
drain piping and corrode the heat exchanger of the
indoor unit.
•
Do not apply external force to the
switch. (It
may result in malfunction)
5. Turn off the power supply after checking drainage,
and remove the power supply wiring.
6. Attach the control box lid as before.
•
Do not touch the electronic parts other than the
terminal block (X2M).
(3) Sweating may occur and result in water leakage.
Therefore, make sure to insulate the following 2
locations (drain piping and drain sockets that laid
indoors).
After drainage is checked, put the attached sealing
material (14) referring to
Fig. 19, and insulate the drain
hose (1) and the metal clamp (2) with the attached sealing
material (Large) (10) referring to
Fig. 21.
Sealing material (14)
(accessory)
Sealing material - Large
(10) (accessory)
Be sure to lay the
sealing material
(10) on (14).
Do not have
the clearance.
Fig. 21
Metal
clamp (2)
Drain hose (1)
(accessory)
Sealing material (Large) (10)
(accessory)
(accessory)
4 mm
≥
8. ELECTRIC WIRING WORK
8-1 GENERAL INSTRUCTIONS
•
Make certain that all electric wiring work is carried out by
qualified
personnel according to the applicable legislation
and this installation manual, using a separate dedicated
circuit.
Insufficient
capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a
fir
e.
•
Make sure to install an earth leakage breaker.
Failure to do so may cause electrical shocks and a
fir
e.
•
Do not turn on the power supply (branch switch, branch
overcurrent circuit breaker) until all the works are
finished.
•
Multiple number of indoor units are connected to one
outdoor unit. Name each indoor unit as A-unit, B-unit ….. and
the like. When these indoor units are wired to the outdoor unit
and the BS unit, always wiring the indoor unit to the terminal
indicated with the same symbol on the terminal block. If the
wiring and the piping are connected to the different indoor
units and operated, it will result in malfunction.
•
Make sure to earth the air conditioner.
Earthing resistance should be according to applicable
legislation.
•
Do not connect the earth wiring to gas or water pipings,
lightning conductor or telephone earth wiring.
•
Gas piping .................Ignition or explosion may occur if
the gas leaks.
•
Water piping ..............Hard vinyl tubes are not effective
earths.
•
Lightning conductor or telephone earth wiring ..................
Electric potential may rise abnormally if struck by a light-
ning bolt.
•
For electric wiring work, refer to also the “WIRING
DIAGRAM” attached to the control box lid.
•
Carry out wiring between the outdoor units, indoor units and
the remote controllers according to the wiring diagram.
•
Carry out installation and wiring of the remote controller
according to the “installation manual” attached to the remote
controller.
•
Do not touch the Printed Circuit Board assembly. It may
cause malfunction.
8-2 ELECTRICAL CHARACTERISTICS
0.3
0.3
0.4
0.4
0.6
1.0
1.4
1.6
1.8
0.3
0.3
0.4
0.4
0.6
1.0
1.4
1.6
1.8
0.2
0.2
0.3
0.3
0.5
0.8
1.1
1.3
1.4
0.2
0.2
0.3
0.3
0.5
0.8
1.1
1.3
1.4
0.053
0.053
0.053
0.053
0.053
0.053
0.106
0.106
0.106
0.053
0.053
0.053
0.053
0.053
0.053
0.106
0.106
0.106
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Units
Power supply
Fan motor
Model
Hz
Volts Voltage
range
MCA MFA
kW
FLA
FXFSQ25AVM
50
220-
240
Max. 264
Min. 198
FXFSQ32AVM
FXFSQ40AVM
FXFSQ50AVM
FXFSQ63AVM
FXFSQ80AVM
FXFSQ100AVM
FXFSQ125AVM
FXFQ25AVM
50
220-
240
Max. 264
Min. 198
FXFQ32AVM
FXFQ40AVM
FXFQ50AVM
FXFQ63AVM
FXFQ80AVM
FXFQ100AVM
FXFQ125AVM
FXFQ140AVM
FXFSQ140AVM
Summary of Contents for FXFSQ-AVM
Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Page 2: ......
Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Page 55: ......