FXFSQ-AVM EDFMT391769A
43
3P468397-1D
10
7. DRAIN PIPING WORK
(1) Carry out drain piping.
Carry out drain piping so that drainage can ensured.
•
Select the piping diameter equal to or larger than
(except for riser) that of the connection piping (polyvinyl
chloride piping, nominal diameter 25 mm, outside
diameter 32 mm).
•
Install the drain piping as short as possible with down-
ward inclination of 1/100 or more and without where air
may stagnate.
(Refer to Fig. 14) (It may cause abnormal
sound such as bubbling noise.)
Downward
inclination of
1/100 or more
1~1.5 m
Support
Good
Wrong
Fig. 14
CAUTION
If drain stagnates in the drain piping, the piping may be
clogged.
CAUTION
Using old drain hose, clamp fixture may cause water
leakage.
•
If
downward inclination cannot be ensured,
carry out upward drain piping.
•
Install supports at a distance of 1 to 1.5 m so that the
piping may no
t deflect.
(Refer to Fig. 14)
•
•
Make sure to use the attached drain hose (1) and the
metal clamp (2).
Insert the drain hose (1) into the drain socket up to the
point where the socket diameter becomes larger.
Put the metal clamp (2) to the taped hose end and
tighten the metal clamp (2) with torque 1.35±0.15 N·m
(135±15
N·cm).
CAUTION
•
Do not tighten the metal clamp (2) with the torque more
than the
value.
The drain hose (1), the socket or the metal clamp (2) may
be damaged.
Metal clamp (2)
(accessory)
Drain socket
VP20 side VP25 side
Hose end
Tape
Drain hose (1)
(accessory)
Fig. 15
< Caution to be taken when carrying out upward drain
piping (Refer to Fig. 16) >
•
The maximum height of the drain riser is 675 mm.
Since the drain pump mounted on this indoor unit is a high
head type, from the characteristic point of view, the higher
the drain riser the lower the draining noise.
Therefore, the drain riser of 300 mm or higher is
recommended.
•
For upward drain piping, keep the horizontal piping
distance of 300 mm or less between the drain socket root
to the drain riser.
Ceiling slab
300 or less
1~1.5 m
Support
Metal clamp (2) (accessory)
Drain hose (1) (accessory)
Upward drain piping
Drain riser
Adjustable
(675 or less)
(850 or less)
Drain hose (1)
(accessory)
Level or upward
inclination
Keep the drain hose level or make a slight up-grade so
that air may not stagnate in the drain hose.
If air stagnates, the drain ma
y flo
w oppositely when
the drain pump stops and generate abnormal sound.
(unit [mm])
Fig. 16
Summary of Contents for FXFSQ-AVM
Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Page 2: ......
Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Page 55: ......