FXFSQ-AVM EDFMT391769A
38
3P468397-1D
5
CAUTION
•
Any vents, light
or other appliances which may
disturb the
might cause ceiling to become dirty if
located too nearby, so follow
Fig. 2 when installing.
Note)
1. This restriction applies to the exposed type lighting, but
does not apply to the recessed type (which does not
protrude below the ceiling line).
2. For how to set the
direction (including
block) with the horizontal blade, refer to “Individual
Direction” in the operation manual attached to
the remote controller.
•
Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least
1 meter away from televisions or radios to prevent image
interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be
to eliminate the noise.)
•
Install the indoor unit as far as possible from
lamps.
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic
lighting type (inverter or rapid start type)
lamp is
installed.
•
Localized temperature difference from the room temperature,
if too large, can affect how the infrare
d floor
sensor judges.
(This may occur, for example, in an area wher
e floor
heating/
high-temperature heat generating equipment is installed.)
•
Each sensor has been set so that the center of the sensing
area is located in the center of the product 800 mm above
the
(in case of the infrared presence sensor) or 0 mm
above the
(in case of the infrared
sensor) when
the ceiling height is approximately 2.7 m.
(2) Ceiling height
•
This indoor unit can be installed in a space of which
ceiling height is up to 3.5 m (Type 100 · 125 · 140 : 4.2 m)
•
However, if the ceiling height exceeds 2.7 m (Type 100 ·
125 · 140 : 3.2 m), it is necessary to set from the remote
controller on site. Refer to the section “
10. FIELD
SETTING AND TEST OPERATION”.
(3) Direction of the air discharge
•
Select the number of directions of the optimum air
discharge for the shape or the position of the room.
•
The number of directions of the air discharge can be
changed by installing a sealing material.
•
When installing a sealing material, the
setting from
the remote controller is required. For details, refer the
operation manual attached to the sealing materials.
(It is set to the setting position number “01” (Standard ·
All round outlet) when shipped from the factory.)
•
To use the optional sealing material kit to change the
setting of air discharge direction (4-way blow type (with
corners sealed)/3-way blow type/2-way blow type), refer
to the installation manual attached to it.
*: Refrigerant piping
*
*
*
[Direction of air discharge]
All round
4-way
3-way
Fig. 3
*
2-way
(4) Use hanging bolts for installation.
Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc.
(Refer to the installation pattern paper (5) for the mounting
pitch.)
(5) Infrared
sensor’s sensing area
The sensing area is as shown in the
below.
800 mm
h
φ
a
φ
b
[Target of detected area]
Infrared floor
sensor
Infrared
presence
sensor
Floor
level
Indoor unit installation height h [m]
2.7
3.5
4.0
Infrared presence sensor
φ
a [m]
Approx.
8.5
Approx.
11.5
Approx.
13.5
Infrared
sensor
φ
b [m]
Approx.
11
Approx.
14
Approx.
16
4. PREPARATION BEFORE INSTALLATION
(1) Check the relation of location between the ceiling
opening and the indoor unit hanging bolts.
950 (Decoration panel)
780 (Hanging bolt pitch)
840 (Indoor unit)
860 – 910 (Ceiling opening)
950 (Decoration panel)
860 – 910 (Ceiling opening)
840 (Indoor unit)
710 (Hanging bolt pitch)
Refrigerant
piping
Hanging
bolt (×4)
A
Fig. 4
Ceiling
View as seen from
A
Hanger
Fig. 5
Decoration Panel
[mm]
BYCQ125EEF/EEK
BYCQ125EAF/EAK
125~130
167~172
180~185
BYCQ125EAPF BYCQ125EASF
(unit [mm])
Summary of Contents for FXFSQ-AVM
Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Page 2: ......
Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Page 55: ......