FXFSQ-AVM EDFMT391769A

37

3P468397-1D

4

2.

Items to be checked at delivery

Items to be checked

Check column

Have you carried out 

field

 setting? (if necessary)

Are the control box lid, the air 

filter

 and the suction 

grille attached?
Does the cool air discharge during the cooling 
operation and the warm air discharge during the 
heating operation? Does the indoor unit makes 
unpleasant sound of air discharge?
Have you explained how to operate the air 
conditioner showing the operation manual to the 
customer? 
Have you explained the description of cooling, 
heating, program dry and automatic (cooling/
heating) given in the operation manual to the 
customer?
If you set the fan speed at thermostat OFF, did you 
explain the set fan speed to the cus tomer.
Have you handed the operation manual and the 
installation manual to the customer?

Points of the operation explanation

In addition to the general usage, since the items in the 

operation manual with the 

WARNING and  

CAUTION marks are likely to result in human bodily 

injuries and property damages, it is neces sary not only 

to explain these items to the customer but also to have 

the customer read them.

2-3  NOTE TO THE INSTALLER

Be sure to instruct customers how to properly operate the unit 

(especially cleaning filters, operating different functions, and 

adjusting the temperature) by having them carry out operations 
themselves while looking at the manual.

The direction of air discharge for this product can be 

selected. Sealing material of air discharge outlet is 

available option for 4-way with sealed corners, 3-way 

and 2-way.

(1) Select the installation location that meets the following

conditions and get approval of the cus tomer.

Where the cool and warm air spreads evenly in the
room.

Where there is no obstacles in the air passage.

Where drainage can be ensured.

Where the ceiling lower surface is not remarkably
inclined.

Where there is 

 strength to withstand the mass

of the indoor unit. (If the strength is 

the

indoor unit may vibrate and get in contact with the ceiling
and generate unpleasant chattering noise.)

Where a space 

 for installation and service can

be ensured. 

(Refer to Fig. 1)

Where the piping length between the indoor and the
outdoor units is ensured within the allowable length.
(Refer to the installation manual attached to the outdoor
unit.)

Where there is no risk of

 gas leak.

Hold the hangers at 4 locations to move the indoor unit 

when unpacking or after unpacked, and do not apply force 

to the piping (refrigerant and drain) and resin parts. 

If the temperature and humidity in the ceiling is likely to 

exceed 30°C, RH80%, use the optional kit for coping with 

high temperature and humidity, or additionally stick the 

insulation to the indoor unit. 

Use the insulation such as glass wool or polyethylene 

that has thickness of 10 mm or more. However, keep the 

insulated outside dimension smaller than the ceiling 

opening so that the unit may go through the opening at 

installation.

3. SELECTION OF INSTALLATION

LOCATION

Required installation space (mm)

Suction Discharge

Discharge 

Floor level

At least 

1800 from

a floor

 

Fig. 1

*≥1500

*≥1500

*≥1500

*≥1500

MODEL NAME

 [mm]

BYCQ125EEF/EEK
BYCQ125EAF/EAK

261

BYCQ125EAPF BYCQ125EASF

FXFSQ25

 · 32 · 40 · 

50

 · 63 · 80AVM

FXFQ

25

 · 32 · 40 · 

50

 · 63 · 80AVM

FXFSQ

25

 · 32 · 40 · 

50

 · 63 · 80AV4

FXFQ

25

 · 32 · 40 · 

50

 · 63 · 80AV4

303

303

345

316

358

Indoor unit

Indoor unit

*1500 or 

more from

a wall

(NOTE)

(Note 1)

Lighting

Exhaust

 fan

At least 1500 

 

from an

y fixture

1500 or 

more

2000 or more

4000  or more

Obstacles

(unit [mm])

Fig. 2

NOTE 

The clearance from the wall (indicated with *) must be

500 mm or more if the air outlet is closed or the horizontal
blade is set to Airflow block and, if the corners (left and right

corners of the target air outlet) are also closed, 200 mm
or more.

FXFSQ100 · 

125

 · 140AVM

FXFQ100 · 

125

 · 140AVM

FXFSQ100 · 

125

 · 140AV4

FXFQ100 · 

125

 · 140AV4

Summary of Contents for FXFSQ-AVM

Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...

Page 2: ......

Page 3: ...s 21 6 Electric Characteristics 22 7 Safety Devices Setting 23 8 Capacity Tables 24 8 1 Cooling Capacity for Te Auto 24 8 2 Cooling Capacity for Te 6 C 24 8 3 Cooling Capacity for Te 9 C 25 8 4 Heatin...

Page 4: ...ty index 25 31 25 40 50 62 5 80 100 125 140 FXFSQ 25AVM 32AVM 40AVM 50AVM 63AVM 80AVM 100AVM 125AVM 140AVM FXFSQ for Thailand 25AVS 32AVS 40AVS 50AVS 63AVS 80AVS 100AVS 125AVS 140AVS FXFSQ for Indones...

Page 5: ...es Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950...

Page 6: ...use Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950 9...

Page 7: ...Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950...

Page 8: ...devices Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 95...

Page 9: ...rigerant control Electronic expansion valve Decoration panel option Model BYCQ125EAF Colour Fresh white Dimensions H W D mm 50 950 950 Air filter Resin net with mould resistance Mass kg 5 5 Standard a...

Page 10: ...FXFSQ AVM EDFMT391769A 8 3 Dimensions 3 1 Standard Panel with Sensing Sensor FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112984A Unit mm...

Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...

Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...

Page 13: ...FXFSQ AVM EDFMT391769A 11 3 2 Standard Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112987A Unit mm...

Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...

Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...

Page 16: ...FXFSQ AVM EDFMT391769A 14 3 3 Designer Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112988A Unit mm...

Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...

Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...

Page 19: ...FXFSQ AVM EDFMT391769A 17 3 4 Auto Grille Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112991A Unit mm...

Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...

Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...

Page 22: ...0AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 12 7 6 4 FXFSQ...

Page 23: ...FXFSQ AVM EDFMT391769A 21 5 Wiring Diagrams FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112965A...

Page 24: ...FXFSQ AVM EDFMT391769A 22 6 Electric Characteristics FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM C 3D112911...

Page 25: ...ector Drain pump thermal protector C Model FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal protector Drain pump thermal protector C...

Page 26: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Page 27: ...city kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of...

Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...

Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...

Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...

Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...

Page 32: ...FXFSQ AVM EDFMT391769A 30 10 Centre of Gravity FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 4D052237S Unit mm...

Page 33: ...long life filter Note 9 10 KAFP55H160H Branch duct chamber Note 4 KDJP55C80 Insulation kit for high humidity Note 9 11 KDTP55K80 C 3D112950A Notes 1 When installing designer panel body height ceiling...

Page 34: ...Branch duct chamber Note 4 KDJP55C160 Insulation kit for high humidity Note 9 11 KDTP55K160 C 3D112950A Notes 1 When installing designer panel body height ceiling required dimension is 42 mm higher th...

Page 35: ...tor for electrical appendices Note 1 KRP4AA53 Installation box for adaptor printed circuit board KRP1H98A Note 2 3 Remote sensor for indoor temperature KRCS01 5B External control adaptor for outdoor u...

Page 36: ...cident due to oxygen de ciency Be sure to use only the speci ed parts and accessories for installation work Failure to use the speci ed parts may result in the air conditioner falling down water leaka...

Page 37: ...angers 4 places and do not apply force to other parts particularly refrigerant piping drain piping and resin parts Make sure to check in advance that the refrigerant to be used for installation work i...

Page 38: ...If you wish to use a remote controller that is not listed in Table 2 on page 3 select a suitable remote controller after consulting catalogs and technical materials CARRY OUT THE WORK GIVING CAUTION T...

Page 39: ...e ensured Where the ceiling lower surface is not remarkably inclined Where there is strength to withstand the mass of the indoor unit If the strength is the indoor unit may vibrate and get in contact...

Page 40: ...controller on site Refer to the section 10 FIELD SETTING AND TEST OPERATION 3 Direction of the air discharge Select the number of directions of the optimum air discharge for the shape or the position...

Page 41: ...olt Ceiling slab Long nut or turn buckle Ceiling surface Note The above shown parts are all eld supply It is easy to attach the optional parts except for decoration panel before installing the indoor...

Page 42: ...Check the level of the unit Refer to Fig 9 5 Remove the washer clamp 7 used for preventing the washer for hanger 3 from dropping and tighten the upper side nut Level Vinyl tube Maintaining horizontal...

Page 43: ...Fig 11 Then turn the nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare nut Union joint Fig 10 Coat the ared inner surface only with ether oil or ester oil Fig 11 Table 3...

Page 44: ...the outdoor unit installation manual or technical document for refrigerant piping 5 In case of refrigerant shortage due to forgetting additional refrigerant charge etc it will result in malfunction su...

Page 45: ...Put the metal clamp 2 to the taped hose end and tighten the metal clamp 2 with torque 1 35 0 15 N m 135 15 N cm CAUTION Do not tighten the metal clamp 2 with the torque more than the value The drain h...

Page 46: ...splashing water on the electric components such as drain pump and con rm drainage by operating the indoor unit under cooling mode according to 10 FIELD SETTING AND TEST OPERATION Refer to Fig 18 100 P...

Page 47: ...dedicated circuit Insuf cient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a re Make sure to install an earth leakage breaker Failure to do s...

Page 48: ...Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXF...

Page 49: ...g transmission wiring connecting method Power supply wiring earth wiring Pull the wiring through the wiring penetrating hole high voltage After connecting the power supply wiring to L N on the power s...

Page 50: ...led off After the wirings are clamped cut off the extra part Sheath peeling off allowance P1 P2 F1 F2 T1 T2 10 15 mm Remote controller wiring Transmission wiring Forced off R10 or more Clamp 4 Remote...

Page 51: ...troller 2 Sub to the terminals P1 P2 for remote controller wiring on the terminal block X1M in the control box Wiring penetrating hole Power supply wiring earth wiring or remote controller wiring tran...

Page 52: ...he SECOND CODE No to 01 4 2 For ON OFF OPERATION set the SECOND CODE No to 02 It is set to FORCE OFF when shipped from the factory Ask your customer to keep the manual attached to the remote controlle...

Page 53: ...ng blade 10 1 SETTING CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 5 Table 5 Setting Ceiling height m Mode No FIRST CODE No SECOND CODE No 25 80 type 100...

Page 54: ...ner until the interior work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives used for the interior...

Page 55: ......

Page 56: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Reviews: