background image

English

9

9.

WIRING EXAMPLE AND HOW TO SET 
THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

Methods of wiring power supply, connecting transmission 

and remote controller wiring

• Power supply wiring

Remove the electric parts box lid shown in the figure, and 
connect to the terminal block (power supply) inside. At this 
time, run the wiring from the power supply side of the guide 
plate to inside the machine.

• Transmission wiring and remote controller wiring

Connect the terminal block (remote controller / transmission 
wiring) so there is no mistake. At this time, run the remote 
controller / transmission wiring from the transmission wiring 
side of the guide plate to inside the machine.

CAUTION

• Be sure to attach the sealing material or putty (field supplied) 

to hole of wiring to prevent the infiltration of water as well as 
any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the electric parts box.

• When clamping the wires, be sure no pressure is applied to 

the wire connections by using the included clamping material 
to make appropriate clamps. Also, when wiring, make sure 
the lid on the electric parts box fits snugly by arranging the 
wires neatly and attaching the electric parts box lid firmly. 
When attaching the electric parts box lid, make sure no wires 
get caught in the edges. Pass wiring through the wiring 
through holes to prevent damage to them.

• Make sure the remote controller wiring, the wiring between 

the units, and other electrical wiring do not pass through the 
same locations outside of the unit, separating them by at 
least 50mm, otherwise electrical noise (external static) could 
cause mistaken operation or breakage. 

CAUTION FOR WIRING

• For connection to the terminal block, use ring type crimp style 

terminals with insulation sleeve or insulate the wirings prop-
erly. 

• Connect the terminal as shown in Fig. 5.

• Do not carry out soldering finish when stranded wires are 

used. (Otherwise, the loosening of wires may result in abnor-
mal heat radiation.) 

(Abnormal heating may occur if the wirings are not tightened 
securely.)

• Use the required wirings, connect them securely and fix 

these wirings securely so that external force may not apply to 
the terminals.

• Use a proper screw driver for tightening the terminal screws. 

If an improper screw driver is used, it may damage the screw 
head and a proper tightening cannot be carried out.

• If a terminal is over tightened, it may be damaged.

Refer to the table shown below for tightening torque of terminals.

Table 5

• Do not carry out soldering finish when stranded wirings are 

used.

WARNING

• When wiring, form the wirings orderly so that the control box 

lid can be securely fastened. If the control box lid is not in 
place, the wirings may come out or be sandwiched by the box 
and the lid and cause electric shocks or a fire.

• Use only specified wire and tightly connect wires to termi-

nals. Be careful wires do not place external stress on termi-
nals. Keep wiring in neat order and so as not to obstruct other 
equipment such as popping open the electric parts box lid. 
Make sure the lid closes tight. Incomplete connections could 
result in overheating, and in worse case, electric shock or 
fire.

 

Power 
supply 
wiring

Terminal block for 
power supply

Electric parts box lid

Electric
parts box

Terminal block for
remote controller wiring

Remote controller wiring
Transmission wiring

Guide 
plate

Ground
wiring

Insulation sleeve

Ring type crimp 
style terminals

Wiring

Fig. 4

Tightening torque (N · m)

Terminal block for remote controller 
and transmission wiring

0.88 ± 0.08

Terminal for power supply

1.47 ± 0.14

Earth terminal

1.69 ± 0.25

Fig. 5

Use wires the same in size 
(if the air conditioner is 
in simultaneous multi operation)

P

1

P

2

F

1

F

2

T

1

T

2

Terminal block for unit
transmission wirings

Clamp

(accessory)

Transmission wiring
between units

Remote controller
wiring (*)

Power supply wiring (*)

Ground terminal

Power supply
terminal block

Field supplied wire

Ground wiring  (*)

01_EN_3P258319-5K.fm  Page 9  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ125MVE

Page 1: ...ORTER ULTÉRI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ...

Page 2: ...E FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV...

Page 3: ... electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installa tion...

Page 4: ...l or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to the installation manual attached to th...

Page 5: ...allowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby so follow the figure below when installing Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televi sions or radios in order to prevent i...

Page 6: ...s 3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit Adjust clearance from the ceiling before proceeding further 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the dec...

Page 7: ...rm steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humi...

Page 8: ...ng Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains flu orine it will damage the refrigerant oil Before brazing local refrigerant piping nitr...

Page 9: ...PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit If converging multiple drain pipes install according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping wor...

Page 10: ...the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosion...

Page 11: ...carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an impr...

Page 12: ...f the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 Outdoor u...

Page 13: ...ndoor units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at f...

Page 14: ... 1511 HT 3P258319 5K EM02A084C ...

Reviews: