[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ]

• Remove the electric parts box lid, connect a power supply 

and remote controller to the terminals. 
(Refer to the “HOW TO CONNECT WIRINGS”)
Be sure attach the electric parts box lid before turning on the 
power.
Next, press the inspection/test operation button “

” on the 

remote controller. The unit will engage the test operation 
mode. Press the operation mode selector button “

” until 

selecting FAN OPERATION “

”. Then, press the ON/OFF 

button “

”. The indoor unit fan and drain pump will start up. 

Check that the water has drained from the unit. Press “

” 

to go back to the first mode.

Be careful when doing so because the fan is turning at 
the same time.

• Attach the electric parts box lid as before.

CAUTION

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

• Keep in mind that it will become the cause of getting drain 

pipe blocked if water collects on drain pipe.

8.

ELECTRIC WIRING WORK 

8-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.

• For electric wiring work, refer to also

 “

Wiring diagram label

” 

attached to the electric parts box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B..., and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. 
If wiring and piping between the outdoor unit and an indoor 
unit are mismatched, the system may cause a malfunction.

• A circuit breaker capable of shutting down power supply to 

the entire system must be installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply wiring connected to the outdoor 
unit, the capacity of the circuit breaker and switch, and wiring 
instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light-

ning rods, or telephone ground wires.

• Gas pipes

 

:

 

might

 

cause explosions or fire if gas leaks.

• Water pipes : no grounding effect if hard vinyl piping is 

used.

• Telephone ground wires or lightning rods : might cause 

abnormally high electric potential in the ground during 
lighting storms.

8-2

ELECTRICAL CHARACTERISTICS

MCA:Min. Circuit Amps (A);  MFA:Max. Fuse Amps (A) 
kW: Fan Motor Rated Output (kW);  FLA:Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

Allowable length of transmission wiring between indoor/outdoor 
units and between the indoor unit and the remote controller is as 
follows. 

(1) Outdoor unit – Indoor unit: 

Max. 1000 m (Total wiring length: 2000 m) 

(2) Indoor unit – Remote controller: 

Max. 500 m

NOTE

1.

Shows only in case of protected piping. Use H07RN-F in 
case of no protection.

2.

Vinyl cord with sheath or cable (Insulated thickness : 1mm 
or more)

Terminal block

220V-240V single
phase power supply

Electric parts 
box lid

TEST

TEST

Units

Power 

supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA MFA

kW

FLA

FXCQ20MVE

50

220-

240

Max. 264
Min.  198

0.5

15 0.010 0.4

FXCQ25 · 32MVE

0.5

15 0.015 0.4

FXCQ40 · 50MVE

0.8

15 0.020 0.6

FXCQ63MVE

0.9

15 0.030 0.7

FXCQ80MVE

1.1

15 0.050 0.9

FXCQ125MVE

1.3

15 0.085 1.0

FXCQ20MVE

60

220

Max. 242
Min.  198

0.5

15 0.010 0.4

FXCQ25 · 32MVE

0.5

15 0.015 0.4

FXCQ40 · 50MVE

0.8

15 0.020 0.6

FXCQ63MVE

0.9

15 0.030 0.7

FXCQ80MVE

1.3

15 0.050 1.0

FXCQ125MVE

1.5

15 0.085 1.2

Model

Power supply wiring

Remote controller 

wiring

Transmission wiring

Field 

fuses  Wire

Size

Wire

Size

FXCQ20MVE

15A

H05VV

-U3G

NOTE 1)

Wiring size 
and length 
must comply 
with local 
codes.

Sheathed wire

(2 wire)

NOTE 2)

0.75 

1.25 

mm

2

FXCQ25 · 32MVE

FXCQ40 · 50MVE

FXCQ63MVE

FXCQ80MVE

FXCQ125MVE

01_EN_3P258319-5K.fm  Page 8  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ125MVE

Page 1: ...ORTER ULTÉRI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ...

Page 2: ...E FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV...

Page 3: ... electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installa tion...

Page 4: ...l or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to the installation manual attached to th...

Page 5: ...allowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby so follow the figure below when installing Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televi sions or radios in order to prevent i...

Page 6: ...s 3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit Adjust clearance from the ceiling before proceeding further 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the dec...

Page 7: ...rm steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humi...

Page 8: ...ng Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains flu orine it will damage the refrigerant oil Before brazing local refrigerant piping nitr...

Page 9: ...PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit If converging multiple drain pipes install according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping wor...

Page 10: ...the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosion...

Page 11: ...carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an impr...

Page 12: ...f the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 Outdoor u...

Page 13: ...ndoor units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at f...

Page 14: ... 1511 HT 3P258319 5K EM02A084C ...

Reviews: