[ For new ceilings ]

(2) Refer to the paper pattern for installation for ceiling 

opening dimension. Consult the builder or carpenter 
for details.

• The center of the ceiling opening is indicated on the 

paper pattern for installation.

• After cutting out a slit for the unit in the center of the paper 

pattern for installation (accessory), install with the 4 
screws (accessory).

• Fold the guide section of paper pattern for installation and 

adjust the height of the unit so the notch in the guide is at 
the position where you expect the ceiling surface to be.

 Ceiling work 

(3) Adjust the unit to the right position for installation. 

(Refer to “

PREPARATIONS BEFORE INSTALLATION-(1)

”.) 

(4) Check the unit is horizontally level.

CAUTION

The indoor unit is equipped with a built-in drain pump 
and float switch. At each of the unit’s 4 corners, verify 
that it is level by using a level or a water-filled vinyl 
tube. (If the unit is inclined against condensate flow, 
the float switch may malfunction and cause water to 
drip.)

(5) Remove the washer fixing plate used for preventing the 

washer from falling and tighten the upper nut.

(6) Remove the paper pattern for installation.

[ For existing ceilings ]

(2) Adjust the height of the unit.

Cut out the guide section of the paper pattern for installation 
attached, place on the bottom surface of the unit, and adjust 
the height of the unit so that the notch of the guide matches 
the lower surface of the ceiling.

(3) Perform steps (3), (4), (5) in For new ceilings.

6.

REFRIGERANT PIPING WORK

• For the outdoor unit refrigerant piping, refer to the installation 

manual attached to the outdoor unit.

• Carry out insulation of both gas and liquid refrigerant piping 

securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C.
For use under high humidity, strengthen the insulation mate-
rial for refrigerant piping. If not strengthened, the surface of 
insulation material may sweat.

• Before installation work, make sure that the refrigerant is 

R410A. (Unless the refrigerant is R410A, the normal opera-
tion cannot be expected.)

CAUTION

This air conditioner is a dedicated model for new refrig-
erant R410A. Make sure to meet the requirements shown 
below and carry out installation work.

Use dedicated piping cutters and flaring tools for 
R410A.

When making a flare connection, coat the flared inner 
surface only with ether oil or ester oil.

Use only the flare nuts attached to the air conditioner. 
If other flare nuts are used, it may cause refrigerant 
leakage.

Part to be procured in the 

fi

eld

[ Securing the hanger bracket ]

Washer (accessory)

Hanger bracket

Tighten
(double nut)

Insert

Washer 

fi

xing plate

(accessory)

[ Securing the washer ]

Cut-out section

Paper pattern
for installation

Screws (× 4 accessory)

(accessory)

[ Installation of paper pattern for installation ]

Guide section (4 corners)

Paper pattern
for installation

Ceiling

Lower 
surface 
of the 
ceiling

[ Unit height adjustment ]

(accessory)

Vinyl tube

Level

The unit body

Ceiling

Lower
surface of 
the ceiling

The guide portion

[ Unit height adjustment ]

01_EN_3P258319-5K.fm  Page 5  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ125MVE

Page 1: ...ORTER ULTÉRI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ...

Page 2: ...E FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV...

Page 3: ... electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installa tion...

Page 4: ...l or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to the installation manual attached to th...

Page 5: ...allowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby so follow the figure below when installing Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televi sions or radios in order to prevent i...

Page 6: ...s 3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit Adjust clearance from the ceiling before proceeding further 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the dec...

Page 7: ...rm steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humi...

Page 8: ...ng Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains flu orine it will damage the refrigerant oil Before brazing local refrigerant piping nitr...

Page 9: ...PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit If converging multiple drain pipes install according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping wor...

Page 10: ...the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosion...

Page 11: ...carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an impr...

Page 12: ...f the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 Outdoor u...

Page 13: ...ndoor units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at f...

Page 14: ... 1511 HT 3P258319 5K EM02A084C ...

Reviews: