background image

English

3

2-3

OPTIONAL ACCESSORIES

• The optional decoration panel and remote controller are 

required for this indoor unit. (Refer to Table 1)

• These are two types of remote controllers: wired and wire-

less. Select a remote controller from Table 2 according to 
customer request and install in an appropriate place.

Table 1

Table 2

NOTE

• If the you wishes to use a remote controller that is not listed 

above, select a suitable remote controller after consulting 
catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL 
CARE DURING CONSTRUCTION AND CHECK 
AFTER INSTALLATION IS FINISHED.

a. Items to be checked after completion of work

b. Items to be checked at time of delivery

Also review the “SAFETY PRECAUTIONS”

c. Points for explanation about operations

2-4

NOTES TO INSTALLER 

Be sure to instruct customers how to properly operate the 
unit (especially cleaning filters, operating different functions, 
and adjusting the temperature) by having them carry out 
operations themselves while looking at the manual. 

3.

SELECTING INSTALLATION SITE 

Please attach additional thermal insulation material to the unit 
body when it is believed that the relative humidity in the ceiling 
exceeds 80%. Use glass wool, polyethylene foam, or similar 
with a thickness of 10 mm or more as thermal insulation mate-
rial.

(1) Select an installation site where the following condi-

tions are fulfilled and that meets with your 
customer’s approval.

• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• In the upper space of the indoor unit where there is no 

possible dripping of water from the refrigerant pipe, drain 
pipe, water pipe, etc.

• If supporting structural members are not strong enough 

to take the unit’s weight, the unit could fall out of place 
and cause serious injury.

• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service 

can be ensured.

• Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation 
manual for the outdoor unit.)

• Any vents, light fixtures, or other appliances which may 

disturb the airflow might cause the top side to become 
dirty if located too nearby, so follow the figure below when 
installing.

• Install the indoor and outdoor units, power supply wiring 

and connecting wires at least 1 meter away from televi-
sions or radios in order to prevent image interference or 
noise.
(Depending on the radio waves, a distance of 1 meter 
may not be sufficient enough to eliminate the noise.)

Model

Optional decoration panel

White

FXCQ20 · 25 · 32MVE

BYBC32GJW1 · BYBC32G-W1

FXCQ40 · 50MVE

BYBC50GJW1 · BYBC50G-W1

FXCQ63MVE

BYBC63GJW1 · BYBC63G-W1

FXCQ80 · 125MVE

BYBC125GJW1 · BYBC125G-W1

Remote controller

Wired type

Wireless type

Heat pump type

Cooling only type 

Items to be checked

If not properly done, what is 
likely to occur

Check

Are the indoor and outdoor 
unit fixed firmly?

The units may drop, vibrate 
or make noise.

Is the gas leak test finished? 

It may result in insufficient 
cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow 
smoothly?

Condensate water may drip.

Does the power supply volt-
age correspond to that 
shown on the name plate?

The unit may malfunction or 
the components burn out.

Are wiring and piping cor-
rect?

The unit may malfunction or 
the components burn out.

Is the unit safely grounded?

Dangerous at electric leak-
age.

Is wiring size according to 
specifications?

The unit may malfunction or 
the components burn out.

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
instruction manual to your customer?

Did you hand the instruction manual over to your cus-
tomer?

The items with  

  WARNING and  

  CAUTION marks 

in the instruction manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
instruction manual.

01_EN_3P258319-5K.fm  Page 3  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ125MVE

Page 1: ...ORTER ULTÉRI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ...

Page 2: ...E FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV...

Page 3: ... electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installa tion...

Page 4: ...l or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to the installation manual attached to th...

Page 5: ...allowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby so follow the figure below when installing Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televi sions or radios in order to prevent i...

Page 6: ...s 3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit Adjust clearance from the ceiling before proceeding further 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the dec...

Page 7: ...rm steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humi...

Page 8: ...ng Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains flu orine it will damage the refrigerant oil Before brazing local refrigerant piping nitr...

Page 9: ...PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit If converging multiple drain pipes install according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping wor...

Page 10: ...the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosion...

Page 11: ...carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an impr...

Page 12: ...f the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 Outdoor u...

Page 13: ...ndoor units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at f...

Page 14: ... 1511 HT 3P258319 5K EM02A084C ...

Reviews: