CONTENTS

1. SAFETY PRECAUTIONS................................................ 1

2. BEFORE INSTALLATION ................................................ 2

3. SELECTING INSTALLATION SITE ................................. 3

4. PREPARATIONS BEFORE INSTALLATION.................... 4

5. INDOOR UNIT INSTALLATION ....................................... 4

6. REFRIGERANT PIPING WORK ..................................... 5

7. DRAIN PIPING WORK .................................................... 7

8. ELECTRIC WIRING WORK ............................................ 8

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER........................................ 9

10. DECORATION PANEL INSTALLATION ......................... 11

11. FIELD SETTINGS ......................................................... 11

12. TEST OPERATION........................................................ 11

The original instructions are written in English. All other lan-
guages are translations of the original instructions.

1.

SAFETY PRECAUTIONS

Be sure to follow this “SAFETY PRECAUTIONS”. 
This product comes under the term “appliances not accessible 
to the general public”.
This is a class A product. In a domestic environment this prod-
uct may cause radio interference in which case the user may be 
required to take adequate measures.

This manual classifies the precautions into WARNINGS and 
CAUTIONS.
Be sure to follow all the precautions below: They are all impor-
tant for ensuring safety.

WARNING

 ............. Indicates a potentially hazardous situ-

ation which, if not avoided, could result 
in death or serious injury.

CAUTION

 .............. Indicates a potentially hazardous situ-

ation which, if not avoided, may result 
in minor or moderate injury.
It may also be used to alert against 
unsafe practices.

• After the installation is completed, test the air conditioner and 

check if the air conditioner operates properly. Give the user 
adequate instructions concerning the use and cleaning of the 
indoor unit according to the Operation Manual. Ask the user 
to keep this manual and the Operation Manual together in a 
handy place for future reference.

WARNING

• Ask your local dealer or qualified personnel to carry out installa-

tion work.
Improper installation may result in water leakage, electric 
shocks or a fire.

• Perform installation work in accordance with this installation 

manual.
Improper installation may result in water leakage, electric 
shocks or a fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage.
When the air conditioner is installed in a small room, it is nec-
essary to take proper measures so that the amount of any 
leaked refrigerant does not exceed the concentration limit in 

the event of a leakage.
Otherwise, this may lead to an accident due to oxygen defi-
ciency.

• Be sure to use only the specified parts and accessories for 

installation work.
Failure to use the specified parts may result in the air condi-
tioner falling down, water leakage, electric shocks, a fire, etc.

• Install the air conditioner on a foundation that can withstand 

its mass.
Insufficient strength may result in the air conditioner falling 
down and causing injury.
In addition, it may lead to vibration of indoor units and cause 
unpleasant chattering noise.

• Carry out the specified installation work in consideration of 

strong winds, typhoons, or earthquakes. Improper installa-
tion may result in an accident such as air conditioner falling.

• Make certain that all electrical work is carried out by qualified 

personnel according to the applicable legislation (note 1) and 
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wir-
ing that has sufficient length and never connect additional 
wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shocks or a fire.
(note 1)

applicable legislation means “All international, 
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a 
certain product or domain”.

• Make sure that all wiring is secure, using the specified wiring 

and ensuring that external forces do not act on the terminal 
connections or wiring.
Incomplete connection or fixing may cause an overheat or a 
fire.

• When wiring the remote controller wiring and transmission 

wiring, and wiring the power supply, form the wiring orderly 
so that the control box cover can be securely fastened.
If the control box cover is not in place, overheat of the termi-
nals, electric shocks or a fire may be caused.

• If refrigerant gas leaks during installation work, ventilate the 

area immediately.
Toxic gas may be produced if refrigerant gas comes into con-
tact with a fire.

• After completing the installation work, check to make sure that 

there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the 
room and comes into contact with a source of a fire, such as a 
fan heater, stove or cooker.

• Disconnect the power supply before touching the electric 

components.
If you touch the live part, you may get an electric shocks.

• Earth the air conditioner.

Do not connect the earth wiring to gas or water piping, light-
ning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage circuit breaker.

Failure to do so may cause electric shocks and a fire.

CAUTION

• Install drain piping according to this installation manual to 

ensure good drainage, and insulate the piping to prevent 
condensation.

01_EN_3P258319-5K.fm  Page 1  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ125MVE

Page 1: ...ORTER ULTÉRI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ...

Page 2: ...E FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV...

Page 3: ... electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installa tion...

Page 4: ...l or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to the installation manual attached to th...

Page 5: ...allowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby so follow the figure below when installing Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televi sions or radios in order to prevent i...

Page 6: ...s 3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit Adjust clearance from the ceiling before proceeding further 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the dec...

Page 7: ...rm steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humi...

Page 8: ...ng Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains flu orine it will damage the refrigerant oil Before brazing local refrigerant piping nitr...

Page 9: ...PRECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit If converging multiple drain pipes install according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping wor...

Page 10: ...the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosion...

Page 11: ...carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an impr...

Page 12: ...f the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 Outdoor u...

Page 13: ...ndoor units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at f...

Page 14: ... 1511 HT 3P258319 5K EM02A084C ...